5
-40
* The factory setting will change when the control method is changed. The flux vector control factory setting is given.
Analog Reference Board: F2
User constants for the Analog Reference Board are shown in the following table.
F1-10
Excessive
speed devia-
tion detec-
tion level
Sets the speed deviation
detection method.
Any speed deviation above
the F1-10 set level (set as a
percentage of the maximum
output frequency) that con-
tinues for the time set in F1-
11 is detected as a speed
deviation.
Speed deviation is the differ-
ence between actual motor
speed and the reference com-
mand speed.
0 to 50
10%
No
No
A
No
A
389H 6-157
F1-11
Excessive
speed devia-
tion detec-
tion delay
time
0.0 to
10.0
0.5 s
No
No
A
No
A
38AH 6-157
F1-12
Number of
PG gear
teeth 1
Sets the number of teeth on
the gears if there are gears
between the PG and the
motor.
A gear ratio of 1 will be used
if either of these constants is
set to 0.
0 to
1000
0
No
No
A
No
No 38BH 6-157
F1-13
Number of
PG gear
teeth 2
0
No
No
A
No
No 38CH 6-157
F1-14
PG open-
circuit
detection
time
Used to set the PG discon-
nection detection time. PGO
will be detected if the detec-
tion time continues beyond
the set time.
0.0 to
10.0
2.0 s
No
No
A
No
A
38DH 6-157
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor
F2-01
Bi-polar or
uni-polar
input selec-
tion
Sets the functions for chan-
nel 1 to 3 which are effective
when the AI-14B Analog
Reference Board is used.
0: 3-channel individual
(Channel 1: terminal A1,
Channel 2: terminal A2,
Channel 3: terminal A3)
1: 3-channel addition (Addi-
tion values are the fre-
quency reference)
When set to 0, select 1 for
b1-01. In this case the multi-
function input “Option/
Inverter selection” cannot be
used.
0 or 1
0
No
A
A
A
A
38FH 6-163
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor
Input pulses from PG 60
F1-13
F1-01
F1-12