5
-84
Note Attach a Momentary Power Interruption Compensation Unit if compensation for power interruptions of up to 2.0 seconds is required for 200 V Class
Inverters with outputs of 0.4 to 11 kW.
* 1. The factory settings when VT is selected are given.
When CT is selected, the factory settings are as follows for Inverters of any capacity:
Carrier frequency selection: 1 (2.0 kHz)
Carrier frequency selection upper limit: 2.5 kHz
* 2. The setting of C6-02 changes the carrier frequency selection as follows:
0: Low-noise PWM, 1: 2.0 kHz, 2: 5.0 kHz, 3: 8.0 kHz, 4: 10.0 kHz, 5: 12.5 kHz, 6: 15.0 kHz
* 3. 95 for Inverter SPEC Type A.
* 4. When setting the carrier frequency of 200 V Class Inverters of 30 kW or more to a value larger than the factory setting, reduce the value of the Inverter
rated output current.
Con-
stant
Number
Name
Unit
Factory Setting
-
Inverter Capacity
kW
18.5
22
30
37
45
55
75
90
110
o2-04
kVA selection
-
9
A
B
C
D
E
F
10
11
b8-03
Energy-saving filter time
constant
s
0.50 (Open loop vector control)
2.00 (Open loop vector control)
b8-04
Energy-saving coeffi-
cient
-
57.87
51.79
46.27
38.16
35.78
31.35
23.10
20.65
18.12
C6-01
CT/VT selection
-
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
C6-02
Carrier frequency selec-
tion (when VT is
selected)
*1 *4
-
6
*2
6
*2
4
*2
3
*2
3
*2
3
*2
2
*2
2
*2
1
*2
-
Carrier frequency selec-
tion upper limit (when
VT is selected)
*1
-
6
6
6
4
4
4
4
4
1
E2-01
(E4-01)
Motor rated current
A
65.8
77.2
105.0
131.0
160.0
190.0
260.0
260.0
260.0
E2-02
(E4-02)
Motor rated slip
Hz
1.67
1.70
1.80
1.33
1.60
1.43
1.39
1.39
1.39
E2-03
(E4-03)
Motor no-load current
A
15.7
18.5
21.9
38.2
44.0
45.6
72.0
72.0
72.0
E2-05
(E4-05)
Motor line-to-line resis-
tance
Ω
0.101
0.079
0.064
0.039
0.030
0.022
0.023
0.023
0.023
E2-06
(E4-06)
Motor leak inductance
%
20.1
19.5
20.8
18.8
20.2
20.5
20.0
20.0
20.0
E2-10
Motor iron loss for
torque compensation
W
505
538
699
823
852
960
1200
1200
1200
L2-02
Momentary power loss
ridethru time
s
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
L2-03
Min. baseblock (BB)
time
s
1.0
1.0
1.1
1.1
1.2
1.2
1.3
1.5
1.7
L2-04
Voltage recovery time
s
0.6
0.6
0.6
0.6
1.0
1.0
1.0
1.0
1.0
L2-08
Frequency reduction
gain at KEB start
°
C
95
95
95
95
95
95
95
95
95
L8-02
Overheat pre-alarm level
°
C
100
90
90
95
100
105
110
100
110
*3
N5-02
Motor acceleration time
s
0.317
0.355
0.323
0.320
0.387
0.317
0.533
0.592
0.646