User Constant Tables
5-
17
* 1. When C6-01 = 0, the upper limit is 150.0.
* 2. When C6-01 = 1, the upper limit is 400.0.
Dwell Functions: b6
User constants for dwell functions are shown in the following table.
* 1. When C6-01 = 0, the upper limit is 150.0.
* 2. When C6-01 = 1, the upper limit is 400.0.
b5-16
PID sleep
operation
delay time
Set the delay time until the
PID sleep function starts in
seconds.
0.0 to
25.5
0.0 s
No
A
A
A
A
1B4H 6-110
b5-17
Accel/decel
time for PID
reference
Set the accel/decel time for
PID reference in seconds.
0.0 to
25.5
0.0 s
No
A
A
A
A
1B5H 6-110
0.0 to
6000.0
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor
b6-01
Dwell
fre-
quency at
start
The dwell function is used to output
frequency temporarily when driving a
motor with a heavy load.
0.0 to
400.0
*1
0.0 Hz
No
A
A
A
A
1B6H
4-20
6-29
0.0 to
300.0
*2
b6-02
Dwell
time at
start
0.0 to
10.0
0.0 s
No
A
A
A
A
1B7H
4-20
6-29
b6-03
Dwell
fre-
quency at
stop
0.0 to
400.0
*1
0.0 Hz
No
A
A
A
A
1B8H
4-20
6-29
0.0 to
300.0
*2
b6-04
Dwell
time at
stop
0.0 to
10.0
0.0 s
No
A
A
A
A
1B9H
4-20
6-29
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor
Run Command
Output frequency
Time
ON
b6-03
OFF
b6-01
b6-04
b6-02