Drive Model
Terminal
Recomm. Gauge
mm
2
(AWG, kcmil)
Wire Range
mm
2
(AWG, kcmil)
Screw
Size
Tightening Torque
N·m (lb.in.)
5A0077
R/L1, S/L2, T/L3
25
(3)
6.0 to 95
(10 to 4/0)
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
25
(3)
6.0 to 95
(10 to 4/0)
⊖
,
⊕
1
–
25 to 95
(3 to 4/0)
⊕
3
–
16 to 95
(6 to 4/0)
25
(4)
25
(4)
5A0099
R/L1, S/L2, T/L3
70
(1/0)
6.0 to 95
(10 to 4/0)
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
50
(1)
6.0 to 95
(10 to 4/0)
⊖
,
⊕
1
–
35 to 95
(2 to 4/0)
⊕
3
–
25 to 95
(4 to 4/0)
25
(4)
25
(4)
5A0125
R/L1, S/L2, T/L3
70
(2/0)
35 to 150
(1 to 300)
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
70
(2/0)
35 to 150
(1 to 300)
⊖
,
⊕
1
–
70
(2/0 to 3/0)
⊕
3
–
35 to 50
(1 to 1/0)
35
(3)
35 to 150
(3 to 300)
5A0145
R/L1, S/L2, T/L3
95
(3/0)
95 to 150
(2/0 to 300)
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
95
(3/0)
95 to 150
(2/0 to 300)
⊖
,
⊕
1
–
70 to 95
(3/0 to 4/0)
⊕
3
–
70 to 95
(1/0 to 2/0)
35
(3)
35 to 150
(3 to 300)
5A0192
R/L1, S/L2, T/L3
185
(300)
95 to 300
(2/0 to 600)
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
150
(250)
95 to 300
(2/0 to 600)
⊖
,
⊕
1
–
95 to 185
(2/0 to 400)
⊕
3
–
95 to 120
(2/0 to 250)
M10
18 to 23
(159 to 204)
50
(1)
35 to 300
(1 to 350)
M12
32 to 40
(283 to 354)
5A0242
R/L1, S/L2, T/L3
240
(400)
95 to 300
(2/0 to 600)
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
185
(350)
95 to 300
(2/0 to 600)
⊖
,
⊕
1
–
95 to 240
(2/0 to 500)
⊕
3
–
150
(250 to 300)
M10
18 to 23
(159 to 204)
50
(1)
35 to 300
(1 to 350)
M12
32 to 40
(283 to 354)
Note:
When connecting peripheral devices or options to terminals
⊖
,
⊕
1,
⊕
3, B1, and B2 , refer to the instruction manual for each device. For
more information, contact Yaskawa or your nearest sales representative.
3.8 Main Circuit Wiring
92
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Содержание P1000
Страница 4: ...This Page Intentionally Blank 4 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 26: ...i 2 General Safety This Page Intentionally Blank 26 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 140: ...4 11 Test Run Checklist This Page Intentionally Blank 140 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 430: ...A 4 Drive Derating Data This Page Intentionally Blank 430 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 504: ...B 16 Defaults by Drive Model This Page Intentionally Blank 504 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 568: ...D 3 UL and CSA Standards This Page Intentionally Blank 568 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 591: ...Index This Page Intentionally Blank YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual 591...
Страница 593: ......