Setting 1: Enabled (6 Hz and above)
Slip compensation is enabled during regenerative operation. It will not be active at output frequencies below 6 Hz.
Setting 2: Enabled (compensation provided wherever possible)
Slip compensation is enabled during regenerative operation and at frequencies as low as 2 Hz. The drive uses the motor rated
slip set to E2-02 to automatically calculate the frequency range where compensation will be disabled.
u
C4: Torque Compensation
The torque compensation function compensates for insufficient torque production at start-up or when a load is applied.
Note:
Set the motor parameters and V/f pattern properly before setting torque compensation parameters.
n
C4-01: Torque Compensation Gain
Sets the gain for the torque compensation function.
No.
Parameter Name
Setting Range
Default
C4-01
Torque Compensation Gain
0.00 to 2.50
1.00
n
C4-02: Torque Compensation Primary Delay Time 1
Sets the delay time used for applying torque compensation.
No.
Parameter Name
Setting Range
Default
C4-02
Torque Compensation Primary Delay Time 1
0 to 60000 ms
200 ms
u
C6: Carrier Frequency
n
C6-02: Carrier Frequency Selection
Sets the switching frequency of the drive output transistors. Changes to the switching frequency lower audible noise and reduce
leakage current.
No.
Parameter Name
Setting Range
Default
C6-02
Carrier Frequency Selection
1 to 9; A, F
7
<1> The setting range is 1, 2, and F for models 4A0930 and 4A1200
Settings:
C6-02
Carrier Frequency
C6-02
Carrier Frequency
C6-02
Carrier Frequency
1
2.0 kHz
5
12.5 kHz
9
Swing PWM 3
2
5.0 kHz
6
15.0 kHz
A
Swing PWM 4
3
8.0 kHz
7
Swing PWM 1
B to E:
No setting possible
4
10.0 kHz
8
Swing PWM 2
F
User defined (C6-03 to C6-05)
Note:
Swing PWM uses a carrier frequency of 2.0 kHz as a base, then applies a special PWM pattern to reduce the audible noise.
Guidelines for Carrier Frequency Parameter Setup
Symptom
Remedy
Speed and torque are unstable at low speeds
Lower the carrier frequency.
Noise from the drive affects peripheral devices
Excessive leakage current from the drive
Wiring between the drive and motor is too long
Audible motor noise is too loud
Increase the carrier frequency or use Swing PWM.
<1> The carrier frequency may need to be lowered if the motor cable is too long. Refer to
rated current is reduced when the carrier frequency is increased.
Table 5.14 Wiring Distance and Carrier Frequency
Wiring Distance
Up to 50 m
Up to 100 m
Greater than 100 m
Recommended setting value for C6-02
1 to F (up to 15 kHz)
1 to 2 (up to 5 kHz),
7 (Swing PWM)
1 (up to 2 kHz), 7 (Swing PWM)
5.3 C: Tuning
180
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Содержание P1000
Страница 4: ...This Page Intentionally Blank 4 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 26: ...i 2 General Safety This Page Intentionally Blank 26 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 140: ...4 11 Test Run Checklist This Page Intentionally Blank 140 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 430: ...A 4 Drive Derating Data This Page Intentionally Blank 430 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 504: ...B 16 Defaults by Drive Model This Page Intentionally Blank 504 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 568: ...D 3 UL and CSA Standards This Page Intentionally Blank 568 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 591: ...Index This Page Intentionally Blank YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual 591...
Страница 593: ......