Setting 0: 156 kbps
Setting 1: 625 kbps
Setting 2: 2.5 Mbps
Setting 3: 5 Mbps
Setting 4: 10 Mbps
n
F6-14: bUS Error Auto Reset
Selects whether a bUS error can be automatically reset if automatic fault retry is enabled.
No.
Parameter Name
Setting Range
Default
F6-14
bUS Error Auto Reset
0, 1
0
Setting 0: Disabled, Auto Reset Not Possible
Setting 1: Enabled, Auto Reset Possible
u
MECHATROLINK Parameters
Parameters F6-20 through F6-26 run the MECHATROLINK options.
n
F6-20: MECHATROLINK Station Address
No.
Parameter Name
Setting Range
Default
F6–20
MECHATROLINK Station Address
20, 3F
21
n
F6-21: MECHATROLINK Frame Size
No.
Parameter Name
Setting Range
Default
F6–21
MECHATROLINK Frame Size
0, 1
0
Setting 0: 32 byte
Setting 1: 17 byte
n
F6-22: MECHATROLINK Link Speed
No.
Parameter Name
Setting Range
Default
F6–22
MECHATROLINK Link Speed
0, 1
0
Setting 0: 10 Mbps
Setting 1: 4 Mbps
n
F6-23 and F6-24: MECHATROLINK Monitor Selection
Sets the output signal level for terminals V1 and V2.
No.
Parameter Name
Setting Range
Default
F6-23
MECHATROLINK–II Monitor Selection (E)
0, FFFF
0
F6-24
MECHATROLINK –II Monitor Selection (F)
0, FFFF
0
n
F6-25: Operation Selection at Watchdog Timer Error
No.
Parameter Name
Setting Range
Default
F6-25
Operation Selection at Watchdog Timer Error (E5)
0 to 3
1
Setting 0: Ramp to stop. Decelerate using the deceleration time in C1-02.
Setting 1: Coast to stop.
Setting 2: Fast stop. Decelerate using the deceleration time in C1-09.
Setting 3: Alarm only
n
F6-26: MECHATROLINK bUS Errors Detected
Sets the number of option communication errors (bUS).
No.
Parameter Name
Setting Range
Default
F6-26
MECHATROLINK bUS Errors Detected
2 to 10
2
5.6 F: Option Settings
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
201
5
Parameter Details
Содержание P1000
Страница 4: ...This Page Intentionally Blank 4 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 26: ...i 2 General Safety This Page Intentionally Blank 26 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 140: ...4 11 Test Run Checklist This Page Intentionally Blank 140 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 430: ...A 4 Drive Derating Data This Page Intentionally Blank 430 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 504: ...B 16 Defaults by Drive Model This Page Intentionally Blank 504 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 568: ...D 3 UL and CSA Standards This Page Intentionally Blank 568 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 591: ...Index This Page Intentionally Blank YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual 591...
Страница 593: ......