u
Three-Phase 400 V Class Drive Models 4A0208 to 4A1200
Table A.6 Power Ratings Continued (Three-Phase 400 V Class)
Item
Specification
Drive Models
4A0208 4A0250 4A0296 4A0362 4A0414 4A0515 4A0675 4A0930 4A1200
Maximum Applicable Motor
Capacity (HP)
ND Rating
150
200
250
300
350
400-450 500-550
750
1000
HD Rating
125-150
150
200
250
300
350
400-450-
500
650
900
Input
Input Current (A)
ND Rating
207
248
300
346
410
465
657
922
1158
HD Rating
170
207
248
300
346
410
584
830
1031
Rated Voltage
Rated Frequency
Three-phase: 380 to 480 Vac 50/60 Hz/510 to 680 Vdc
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency Fluctuation
±5%
Input Power (kVA)
ND Rating
189
227
274
316
375
425
601
843
1059
HD Rating
155
189
227
274
316
375
534
759
943
Output
Rated Output Capacity
(kVA)
ND Rating
189
227
274
316
375
425
601
843
1059
HD Rating
137
165
198
232
282
343
461
617
831
Rated Output Current
(A)
ND Rating
208
250
296
362
414
515
675
930
1200
HD Rating
180
216
260
304
370
450
605
810
1090
Overload Tolerance
ND Rating: 120% of rated output current for 60 s
HD Rating: 150% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency
User-adjustable between 1 and 10 kHz
User-adjustable between 1 and 5 kHz
Maximum Output Voltage (V)
Three-phase: 380 to 480 Vac (proportional to input voltage)
0.95 ×
[input voltage]
Maximum Output Frequency (Hz)
400 Hz (user-adjustable)
<3> DC input is not available for UL standards.
<4> Rated motor capacity is calculated with a rated output voltage of 440 V.
<5> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<6> Carrier frequency can be increased to 5 kHz while keeping this current derating. Higher carrier frequency settings require derating.
<7> Carrier frequency can be increased to 5 kHz while keeping this current derating. Higher carrier frequency settings require derating.
A.1 Power Ratings
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
399
A
Specifications
Содержание P1000
Страница 4: ...This Page Intentionally Blank 4 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 26: ...i 2 General Safety This Page Intentionally Blank 26 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 140: ...4 11 Test Run Checklist This Page Intentionally Blank 140 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 430: ...A 4 Drive Derating Data This Page Intentionally Blank 430 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 504: ...B 16 Defaults by Drive Model This Page Intentionally Blank 504 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 568: ...D 3 UL and CSA Standards This Page Intentionally Blank 568 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 591: ...Index This Page Intentionally Blank YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual 591...
Страница 593: ......