Digital Operator Display
Minor Fault Name
rUn
Motor Switch during Run
A command to switch motors was entered during run.
Cause
Possible Solutions
A motor switch command was entered
during run.
Change the operation pattern so that the motor switch command is entered while the drive is stopped.
Digital Operator Display
Minor Fault Name
SE
MEMOBUS/Modbus Communication Test Mode Error
Note:
This alarm will not trigger a multi-function output terminal that is set for alarm output
(H2-
oo
= 10).
Cause
Possible Solutions
A digital input set to 67H (MEMOBUS/
Modbus test) was closed while the drive
was running.
Stop the drive and run the test again.
Digital Operator Display
Minor Fault Name
TrPC
IGBT Maintenance Time (90%)
IGBTs have reached 90% of their expected performance life.
Cause
Possible Solutions
IGBTs have reached 90% of their expected
performance life.
Replace the drive.
Digital Operator Display
Minor Fault Name
Uv
Undervoltage
One of the following conditions was true when the drive was stopped and a Run command was entered:
• DC bus voltage dropped below the level specified in L2-05.
• Contactor to suppress inrush current in the drive was opened.
• Low voltage in the control drive input power. This alarm outputs only if L2-01 is not 0 and DC bus voltage
is under L2-05.
Cause
Possible Solutions
Phase loss in the drive input power.
Check for wiring errors in the main circuit drive input power. Correct the wiring.
Loose wiring in the drive input power
terminals.
• Ensure the terminals have been properly tightened.
• Apply the tightening torque to the terminals as specified.
Refer to Main Circuit Wire Gauges and
There is a problem with the drive input
power voltage.
• Check the voltage.
• Lower the voltage of the drive input power so that it is within the limits listed in the specifications.
Drive internal circuitry is worn.
• Check the maintenance time for the capacitors (U4-05).
• Replace either the control board or the entire drive if U4-05 exceeds 90%. For instructions on replacing
the control board, contact Yaskawa or your nearest sales representative.
The drive input power transformer is too
small and voltage drops when the power is
switched on.
• Check for an alarm when the magnetic contactor, line breaker, and leakage breaker are closed.
• Check the capacity of the drive input power transformer.
Air inside the drive is too hot.
Check the temperature inside the drive.
The CHARGE light is broken or
disconnected.
Replace either the control board or the entire drive. For instructions on replacing the control board, contact
Yaskawa or your nearest sales representative.
Digital Operator Display
Minor Fault Name
WrUn
Waiting for Run
Cause
Possible Solutions
The Run command has been applied and
the b1-11 timer is active.
Adjust b1-11 to the desired delay time. The drive sill start normally after the b1-11 timer expires.
Digital Operator Display
Minor Fault Name
1PH
1-Phase Foldback
<0x5A>
Output speed is being limited because of excessive DC bus voltage ripple.
Cause
Possible Solutions
6.5 Alarm Detection
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
317
6
Troubleshooting
Содержание P1000
Страница 4: ...This Page Intentionally Blank 4 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 26: ...i 2 General Safety This Page Intentionally Blank 26 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 140: ...4 11 Test Run Checklist This Page Intentionally Blank 140 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 430: ...A 4 Drive Derating Data This Page Intentionally Blank 430 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 504: ...B 16 Defaults by Drive Model This Page Intentionally Blank 504 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 568: ...D 3 UL and CSA Standards This Page Intentionally Blank 568 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 591: ...Index This Page Intentionally Blank YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual 591...
Страница 593: ......