Verifying the New Time Setting
After pressing ENTER , the display will indicate “Entry accepted” and the new time value will be saved to the Real-Time
Clock (RTC).
If there is a problem with the entered time, the operator will indicate “Input error” and the screen will return to the time setting
display.
Canceling the Input
Pressing the ESC key will display “Aborted” on the operator, and no value will be saved to the RTC. Pressing OFF will abort
the setting process without any display, and no setting changes will be saved to the RTC.
Exiting from the Time Setting Screen Without Making Any Changes
If no changes are entered, the display will exit Real Time Clock Adjustment Display after a few seconds and no changes will
be saved.
n
Real-Time Clock Setting at Initial Power-up of a New Drive
Setting the Real-time clock is required at power-up of a new drive or after keypad battery replacement.
illustrates how to set the Real-Time Clock at initial power-up of a new drive.
Table 4.4 Clock Adjustment Procedure at Power-up of a New Drive
Procedure
Display
1
Turn the power on. The Real Time Clock Adjustment Display will appear. Use the right arrow
key to select the desired digit, then set the correct date and time using the up and down arrow
keys.
ALM
20
1
0/01/01 00:00
Second per month
+ 0 sec
YYYY/MM/DD HH:MM
ALM
2
After entering the Real-Time Clock data, press the ENTER key to save the changes.
The display will indicate “Entry Accepted” and return to the initial display in step 3 and the alarm
LED will be OFF.
ALM
Entry accepted
3
Initial display.
- MODE -
U1-01= 0.00Hz
U1-02= 0.00Hz
U1-03= 0.00 A
DRV
Freq Ref (AI)
Rdy
FWD
LSEQ
LREF
n
Manual Clock Adjustment by Setting o4-17 to 1
The following actions are possible in the Clock Adjustment Mode:
• Set the current time
• Check the time set to the drive Real-Time Clock
illustrates how to set the Real-Time Clock manually.
Table 4.5 Manual Clock Adjustment Procedure by Setting o4-17 to 1
Procedure
Display
1
The “Time Not Set” (TIM) display will appear if the Real-Time Clock data is not entered within
30 seconds of power-up on a new drive.
Refer to
for details on the TIM display.
- MODE -
Time Not Set
RESET
DRV
ALM
TIM
FWD
ALM
2
Use the up and down arrow keys to scroll through display menu until the screen shows
“Programming”.
- MODE -
HOME
PRG
ALM
Programming
FWD
4.3 The Drive, Programming, and Clock Adjustment Modes
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
115
4
Start-Up Programming & Operation
Содержание P1000
Страница 4: ...This Page Intentionally Blank 4 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 26: ...i 2 General Safety This Page Intentionally Blank 26 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 140: ...4 11 Test Run Checklist This Page Intentionally Blank 140 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 430: ...A 4 Drive Derating Data This Page Intentionally Blank 430 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 504: ...B 16 Defaults by Drive Model This Page Intentionally Blank 504 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 568: ...D 3 UL and CSA Standards This Page Intentionally Blank 568 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 591: ...Index This Page Intentionally Blank YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual 591...
Страница 593: ......