7.5 Drive Replacement
u
Serviceable Parts
The drive contains some serviceable parts. The following parts can be replaced over the life span of the drive:
• Terminal board I/O PCBs
• Cooling fan(s)
• Front cover
Replace the drive if the main power circuitry is damaged. Contact your local Yaskawa representative before replacing parts
if the drive is still under warranty. Yaskawa reserves the right to replace or repair the drive according to Yaskawa warranty
policy.
u
Terminal Board
The drive has a modular I/O terminal block that facilitates quick drive replacement. The terminal board contains on-board
memory that stores all drive parameter settings and allows the parameters to be saved and transferred to the replacement drive.
To transfer the terminal board, disconnect the terminal board from the damaged drive and reconnect it to the replacement
drive. There is no need to manually reprogram the replacement drive after transferring the terminal board.
Note:
If the damaged drive and the new replacement drive are have different capacities, the data stored in the terminal board cannot be transferred
to the new drive and an oPE01 error will appear on the display. The terminal board can still be used, but parameter setting from the old
drive cannot be transferred. The replacement drive must be initialized and manually programmed.
A
B
C
F
D
E
A – Removable terminal board
B – Charge LED
C – Conduit bracket
D – Conduit bracket cover screws
E – Conduit bracket mounting screws
F – Terminal board locking screws
Figure 7.52 Terminal Board
7.5 Drive Replacement
370
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Содержание P1000
Страница 4: ...This Page Intentionally Blank 4 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 26: ...i 2 General Safety This Page Intentionally Blank 26 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 140: ...4 11 Test Run Checklist This Page Intentionally Blank 140 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 430: ...A 4 Drive Derating Data This Page Intentionally Blank 430 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 504: ...B 16 Defaults by Drive Model This Page Intentionally Blank 504 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 568: ...D 3 UL and CSA Standards This Page Intentionally Blank 568 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 591: ...Index This Page Intentionally Blank YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual 591...
Страница 593: ......