No.
(Addr.
Hex)
Name
Description
Values
Page
d1-17
(292)
Jog Frequency Reference
Sets the Jog frequency reference. Setting units are determined by parameter
o1-03.
Default: 6.00 Hz
Min.: 0.00
Max.: 400.00
u
d2: Frequency Upper/Lower Limits
No.
(Addr.
Hex.)
Name
Description
Setting
Page
d2-01
(289)
Frequency Reference Upper
Limit
Sets the frequency reference upper limit as a percentage of the maximum
output frequency.
Default: 100.0%
Min.: 0.0
Max.: 110.0
d2-02
(28A)
Frequency Reference Lower
Limit
Sets the frequency reference lower limit as a percentage of the maximum
output frequency.
Default: 0.0%
Min.: 0.0
Max.: 110.0
d2-03
(293)
Master Speed Reference
Lower Limit
Sets the lower limit for frequency references from analog inputs as a
percentage of the maximum output frequency.
Default: 0.0%
Min.: 0.0
Max.: 110.0
u
d3: Jump Frequency
No.
(Addr.
Hex)
Name
Description
Values
Page
d3-01
(294)
Jump Frequency 1
Eliminates problems with resonant vibration of the motor/machine by
avoiding continuous operation in predefined frequency ranges. The drive
accelerates and decelerates the motor through the prohibited frequency ranges.
Setting 0.0 disables this function.
Parameters must be set so that d3-01 ≥ d3-02 ≥ d3-03.
Default: 0.0 Hz
Min.: 0.0
Max.: 400.0
d3-02
(295)
Jump Frequency 2
Eliminates problems with resonant vibration of the motor/machine by
avoiding continuous operation in predefined frequency ranges. The drive
accelerates and decelerates the motor through the prohibited frequency ranges.
Setting 0.0 disables this function.
Parameters must be set so that d3-01 ≥ d3-02 ≥ d3-03.
Default: 0.0 Hz
Min.: 0.0
Max.: 400.0
d3-03
(296)
Jump Frequency 3
Eliminates problems with resonant vibration of the motor/machine by
avoiding continuous operation in predefined frequency ranges. The drive
accelerates and decelerates the motor through the prohibited frequency ranges.
Setting 0.0 disables this function.
Parameters must be set so that d3-01 ≥ d3-02 ≥ d3-03.
Default: 0.0 Hz
Min.: 0.0
Max.: 400.0
d3-04
(297)
Jump Frequency Width
Sets the dead-band width around each selected prohibited frequency reference
point.
Default: 1.0 Hz
Min.: 0.0
Max.: 20.0
u
d4: Frequency Reference Hold and Up/Down 2 Function
No.
(Addr.
Hex)
Name
Description
Values
Page
d4-01
(298)
Frequency Reference Hold
Function Selection
0: Disabled. Drive starts from zero when the power is switched on.
1: Enabled. At power up, the drive starts the motor at the Hold frequency that
was saved.
Default: 0
Range: 0, 1
d4-03
(2AA)
Frequency Reference Bias
Step (Up/Down 2)
Sets the bias added to the frequency reference when the Up 2 and Down 2
digital inputs are enabled (H1-
oo
= 75, 76).
Default: 0.00 Hz
Min.: 0.00
Max.: 99.99
d4-04
(2AB)
Frequency Reference Bias
Accel/Decel (Up/Down 2)
0: Use selected accel/decel time.
1: Use accel/decel time 4 (C1-07 and C1-08).
Note:
The functionality of setting 1 is only accessible via
MEMOBUS/Modbus communication.
Default: 0
Range: 0, 1
B.5 d: References
444
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Содержание P1000
Страница 4: ...This Page Intentionally Blank 4 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 26: ...i 2 General Safety This Page Intentionally Blank 26 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 140: ...4 11 Test Run Checklist This Page Intentionally Blank 140 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 430: ...A 4 Drive Derating Data This Page Intentionally Blank 430 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 504: ...B 16 Defaults by Drive Model This Page Intentionally Blank 504 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 568: ...D 3 UL and CSA Standards This Page Intentionally Blank 568 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 591: ...Index This Page Intentionally Blank YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual 591...
Страница 593: ......