4.4 Start-Up Flowchart
summarizes steps required to start the drive and gives quick references to help familiarize the user with start-up
procedures.
YES
NO
START
Install and wire the drive as explained in Chapters 1, 2, and 3.
Apply main power to the drive while following safety guidelines.
Application Presets
A1-03 used?
Refer to
Application
Selection Section
Set the basic parameters
b1-01/b1-02
for frequency reference selection and run command source selection
H1-
oo
,H2-
oo
,H3-
oo
,H4-
oo
,H6-
oo
for I/O terminal setting
d1-
oo
for using multi-speed references
C1-
oo
and C2-
oo
for accel/decel and S-curve time settings
L8-55 = 0
if using a regen converter
L3-04
if using dynamic braking options
NO
YES
YES
NO
Run the motor without load; check the rotation direction and operation.
Verify external signal commands to the drive work as desired.
Couple the load or machine to the motor.
Run the machine and check for desired operation.
Fine tune parameters. Adjust application settings if necessary.
Check the machine operation and verify parameter settings.
Drive is ready to run the application.
Energy Savings (b8-01 = 1)
or Speed Estimation Search (b3-24 = 1)
enabled when b3-01 = 1 or L2-01 = 1, 2?
Is the motor cable
longer than 50 meters?
Set or verify the V/f pattern settings E1-
oo
.
Perform Rotational Auto-Tuning
for V/f Control (T1-01 = 3)
Perform Stationary Auto-Tuning
for Stator Resistance (T1-01 = 2)
Figure 4.9 Simple Setup with Energy Savings or Speed Search
Note:
1.
Execute Stationary Auto-Tuning for Line-to-Line Resistance if the drive has been Auto-Tuned and then moved to a different location
where the motor cable length exceeds 50 m.
2.
Perform Auto-Tuning again after installing an AC reactor or other such components to the output side of the drive.
4.4 Start-Up Flowchart
124
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Содержание P1000
Страница 4: ...This Page Intentionally Blank 4 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 26: ...i 2 General Safety This Page Intentionally Blank 26 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 140: ...4 11 Test Run Checklist This Page Intentionally Blank 140 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 430: ...A 4 Drive Derating Data This Page Intentionally Blank 430 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 504: ...B 16 Defaults by Drive Model This Page Intentionally Blank 504 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 568: ...D 3 UL and CSA Standards This Page Intentionally Blank 568 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 591: ...Index This Page Intentionally Blank YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual 591...
Страница 593: ......