No.
(Addr.
Hex)
Name
Description
Values
Page
S2-06
(320B)
Sequence Timer 2 Start
Time
Sets the start time for timer 2. The value must be set less than or equal to S2-07. Default: 00:00
Min.: 00:00
Max.: 24:00
S2-07
(320C)
Sequence Timer 2 Stop Time
Sets the stop time for timer 2. The value must be set greater than or equal to
S2-06.
Default: 00:00
Min.: 00:00
Max.: 24:00
S2-08
(320D)
Sequence Timer 2 Day
Selection
Sets the days for which sequence timer 2 is active.
0: Timer disabled
1: Daily
2: Mon - Fri
3: Sat - Sun
4: Monday
5: Tuesday
6: Wednesday
7: Thursday
8: Friday
9: Saturday
10: Sunday
Default: 0
Range: 0 to 10
S2-09
(320E)
Sequence Timer 2 Selection
Sets the action that occurs when sequence timer 2 is active.
0: Digital output only
1: Run
2: Run - PI disable
Default: 0
Range: 0 to 2
S2-10
(320F)
Sequence Timer 2 Reference
Source
Selects the frequency reference source used for running the drive when
sequence timer 2 is active (only applicable when S2-09 is set to 1 or 2).
0: Operator (d1-01)
1: Operator (d1-02)
2: Operator (d1-03)
3: Operator (d1-04)
4: Terminals
5: Serial communication
6: Option card
7: Pulse input
Default: 0
Range: 0 to 7
S2-11
(3210)
Sequence Timer 3 Start
Time
Sets the start time for timer 3. The value must be set less than or equal to S2-12. Default: 00:00
Min.: 00:00
Max.: 24:00
S2-12
(3211)
Sequence Timer 3 Stop Time
Sets the stop time for timer 3. The value must be set greater than or equal to
S2-11.
Default: 00:00
Min.: 00:00
Max.: 24:00
S2-13
(3212)
Sequence Timer 3 Day
Selection
Sets the days for which sequence timer 3 is active.
0: Timer disabled
1: Daily
2: Mon - Fri
3: Sat - Sun
4: Monday
5: Tuesday
6: Wednesday
7: Thursday
8: Friday
9: Saturday
10: Sunday
Default: 0
Range: 0 to 10
S2-14
(3213)
Sequence Timer 3 Selection
Sets the action that occurs when sequence timer 3 is active.
0: Digital output only
1: Run
2: Run - PI disable
Default: 0
Range: 0 to 2
S2-15
(3214)
Sequence Timer 3 Reference
Source
Selects the frequency reference source used for running the drive when
sequence timer 3 is active (only applicable when S2-14 is set to 1 or 2).
0: Operator (d1-01)
1: Operator (d1-02)
2: Operator (d1-03)
3: Operator (d1-04)
4: Terminals
5: Serial communication
6: Option card
7: Pulse input
Default: 0
Range: 0 to 7
S2-16
(3215)
Sequence Timer 4 Start
Time
Sets the start time for timer 4. The value must be set less than or equal to S2-17. Default: 00:00
Min.: 00:00
Max.: 24:00
B.12 S: Special Application
474
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Содержание P1000
Страница 4: ...This Page Intentionally Blank 4 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 26: ...i 2 General Safety This Page Intentionally Blank 26 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 140: ...4 11 Test Run Checklist This Page Intentionally Blank 140 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 430: ...A 4 Drive Derating Data This Page Intentionally Blank 430 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 504: ...B 16 Defaults by Drive Model This Page Intentionally Blank 504 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 568: ...D 3 UL and CSA Standards This Page Intentionally Blank 568 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 591: ...Index This Page Intentionally Blank YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual 591...
Страница 593: ......