10 s
etc.
time
10 s
10 s
10 s
10 s
10 s
10 s
f
ref
× (L8-19)
f
ref
× (L8-19)
2
f
ref
× (L8-19)
4
f
ref
× (L8-19)
3
f
ref
Output frequency
Reset oH
Alarm
Reset oH
Alarm
Digital output (4D)
oH
Alarm
oH
Alarm
oH
Alarm
oH
Alarm
oH alarm number
Figure 5.84 Output Frequency Reduction During Overheat Alarm
n
L8-19: Frequency Reduction Rate during Overheat Pre-Alarm
Specifies the output frequency reduction when L8-03 is set to 4 and an oH alarm is present.
No.
Name
Setting Range
Default
L8-19
Frequency Reduction Rate During Overheat Pre-Alarm
0.1 to 0.9
0.8
n
L8-05: Input Phase Loss Protection Selection
Enables or disables the input phase loss detection.
No.
Name
Setting Range
Default
L8-05
Input Phase Loss Protection Selection
0, 1
1
Setting 0: Disabled
Setting 1: Enabled
Enables input phase loss detection. Since measuring the DC bus ripple detects input phase loss, a power supply voltage
imbalance or main circuit capacitor deterioration may also trigger a phase loss fault (PF).
Detection is disabled if:
• The drive is decelerating.
• No Run command is active.
• Output current is less than or equal to 30% of the drive rated current.
n
L8-07: Output Phase Loss Protection Selection
Enables or disables the output phase loss detection triggered when the output current falls below 5% of the drive rated current.
Note:
Output phase loss detection can mistakenly be triggered if the motor rated current is very small compared to the drive rating. Disable this
parameter in such cases.
No.
Name
Setting Range
Default
L8-07
Output Phase Loss Protection Selection
0 to 2
1
Setting 0: Disabled
Setting 1: Fault when One Phase Is Lost
An output phase loss fault (LF) is triggered when one output phase is lost. The output shuts off and the motor coasts to stop.
5.8 L: Protection Functions
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
259
5
Parameter Details
Содержание P1000
Страница 4: ...This Page Intentionally Blank 4 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 26: ...i 2 General Safety This Page Intentionally Blank 26 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 140: ...4 11 Test Run Checklist This Page Intentionally Blank 140 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 430: ...A 4 Drive Derating Data This Page Intentionally Blank 430 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 504: ...B 16 Defaults by Drive Model This Page Intentionally Blank 504 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 568: ...D 3 UL and CSA Standards This Page Intentionally Blank 568 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 591: ...Index This Page Intentionally Blank YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual 591...
Страница 593: ......