B.11 o: Operator-Related Settings
The o parameters set up the digital operator displays.
u
o1: Digital Operator Display Selection
No.
(Addr.
Hex)
Name
Description
Values
Page
o1-01
(500)
Drive Mode Unit Monitor
Selection
Selects the content of the last monitor that is shown when scrolling through
Drive Mode display. Enter the last three digits of the monitor parameter
number to be displayed: U
o
-
oo
.
Default: 106
(Monitor U1-06)
Range: 104 to 809
o1-02
(501)
User Monitor Selection after
Power Up
1: Frequency reference (U1-01)
2: Direction
3: Output frequency (U1-02)
4: Output current (U1-03)
5: User-selected monitor (set by o1-01)
Default: 1
Range: 1 to 5
o1-03
(502)
Digital Operator Display
Selection
Sets the units the drive should use to display the frequency reference and motor
speed monitors.
0: 0.01 Hz
1: 0.01% (100% = E1-04)
2: r/min (calculated using the number of motor poles setting in E2-04)
3: User-selected units (set by o1-09, o1-10 and o1-11)
Default: 0
Range: 0 to 3
o1-05
(0504)
LCD Contrast Control
Sets the contrast of the LCD operator.
Default: 3
Min.: 0
Max.: 5
o1-06
(517)
User Monitor Selection
Mode
Selects the monitors displayed on the second and third lines of the digital
operator display.
0: 3 Monitor Sequential (displays the next two sequential monitors)
1: 3 Monitor Selectable (set by o1-07 and o1-08)
Default: 0
Range: 0, 1
o1-07
(518)
Second Line Monitor
Selection
Selects the monitor that is shown in the second line.
Enter the last three digits of the monitor parameter number to be displayed:
U
o
-
oo
. For example, set "403" to display monitor parameter U4-03.
Note:
Parameter is effective only when o1-06 is set to 1.
Default: 102
Range: 101 to 799
o1-08
(519)
Third Line Monitor
Selection
Selects the monitor that is shown in the third line.
Enter the last three digits of the monitor parameter number to be displayed:
U
o
-
oo
. For example, set "403" to display monitor parameter U4-03.
Note:
Parameter is effective only when o1-06 is set to 1.
Default: 103
Range: 101 to 799
o1-09
(51C)
Frequency Reference
Display Units
Sets unit display for the frequency reference parameters and frequency related
monitors when o1-03 = 3.
0: WC (Inch of water)
1: PSI (Pounds per square inch)
2: GPM (Gallons per minute)
3: F (Degrees Fahrenheit)
4: CFM (Cubic feet per minute)
5: CMH (Cubic meters per hour)
6: LPH (Liters per hour)
7: LPS (Liters per second)
8: Bar (Bar)
9: Pa (Pascal)
10: C (Degrees Celsius)
11: Mtr (Meters)
12: Ft (Feet)
13: LPM (Liters per minute)
14: CMM (Cubic meters per minute)
15: “Hg (inches of mercury)
24: Custom units (determined by o1-13 to o1-15)
25: None
Default: 25
Range: 0 to 15; 24,
25
o1-10
(520)
User-Set Display Units
Maximum Value
These settings define the display values when o1-03 is set to 3.
o1-10 sets the display value that is equal to the maximum output frequency.
o1-11 sets the position of the decimal position.
Default:
Range: 1 to 60000
o1-11
(521)
User-Set Display Units
Decimal Display
Default:
Range: 0 to 3
o1-13
(3105)
Frequency Reference and
Frequency Related Monitor
Custom Units 1
Sets the first character of the customer-specified unit display when o1-03 is
set to 3 and o1-09 is set to 24.
Default: 41
Range: 30 to 7A
B.11 o: Operator-Related Settings
470
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Содержание P1000
Страница 4: ...This Page Intentionally Blank 4 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 26: ...i 2 General Safety This Page Intentionally Blank 26 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 140: ...4 11 Test Run Checklist This Page Intentionally Blank 140 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 430: ...A 4 Drive Derating Data This Page Intentionally Blank 430 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 504: ...B 16 Defaults by Drive Model This Page Intentionally Blank 504 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 568: ...D 3 UL and CSA Standards This Page Intentionally Blank 568 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 591: ...Index This Page Intentionally Blank YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual 591...
Страница 593: ......