No.
Name
Setting Range
Default
T1-03
Motor Rated Voltage
0.0 to 255.5 V
200.0 V
n
T1-04: Motor Rated Current
Sets the motor rated current according to the motor nameplate value. Enter the current at the motor base speed.
No.
Name
Setting Range
Default
T1-04
Motor Rated Current
10 to 200% of drive rated
current
o2-04
n
T1-05: Motor Base Frequency (T1-01 = 2)
Sets the motor rated frequency according to the motor nameplate value. If a motor with an extended speed range is used or
the motor is used in the field weakening area, enter the maximum frequency to E1-04 after Auto-Tuning is complete.
No.
Name
Setting Range
Default
T1-05
Motor Base Frequency
0.0 to 400.0 Hz
60.0 Hz
n
T1-06: Number of Motor Poles (T1-01 = 3)
Sets the number of motor poles according to the motor nameplate value.
No.
Name
Setting Range
Default
T1-06
Number of Motor Poles
2 to 48
4
n
T1-07: Motor Base Speed (T1-01 = 3)
Sets the motor rated speed according to the motor nameplate value. Enter the speed at base frequency when using a motor
with an extended speed range or if using the motor in the field weakening area.
No.
Name
Setting Range
Default
T1-07
Motor Base Speed
1750 r/min
n
T1-11: Motor Iron Loss
Provides iron loss information to determine the Energy Saving coefficient. T1-11 will first display the value for the motor iron
loss that was automatically calculated when motor capacity was entered to T1-02. Enter the motor iron loss value listed to
T1-11 if the motor test report is available.
No.
Name
Setting Range
Default
T1-11
Motor Iron Loss
0 to 65535 W
14 W Differs
depending on motor
code and motor
parameter settings.
4.7 Auto-Tuning
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
133
4
Start-Up Programming & Operation
Содержание P1000
Страница 4: ...This Page Intentionally Blank 4 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 26: ...i 2 General Safety This Page Intentionally Blank 26 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 140: ...4 11 Test Run Checklist This Page Intentionally Blank 140 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 430: ...A 4 Drive Derating Data This Page Intentionally Blank 430 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 504: ...B 16 Defaults by Drive Model This Page Intentionally Blank 504 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 568: ...D 3 UL and CSA Standards This Page Intentionally Blank 568 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 591: ...Index This Page Intentionally Blank YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual 591...
Страница 593: ......