No.
Name
Unit
–
Model CIMR-P
o
–
5A0003
5A0004
5A0006
5A0009
5A0011
o2-04
Drive Model Selection
Hex.
C3
C4
C5
C7
E2-11
Motor Rated Power
kW
(HP)
1.5
(2)
2.2
(3)
3.7
(5)
5.5
(7.5)
7.5
(10)
L2-04
Momentary Power Loss Voltage Recovery
Time
s
0.5
0.5
0.6
0.7
0.8
L3-24
Motor Acceleration Time for Inertia
Calculations
s
0.166
0.145
0.154
0.168
0.175
L8-02
Overheat Alarm Level
°C
110
110
110
110
115
L8-35
Installation Method Selection
–
2
2
2
2
2
L8-38
Carrier Frequency Reduction Selection
–
2
2
2
2
2
n1-03
Hunting Prevention Time Constant
ms
10
10
10
10
10
B.16 Defaults by Drive Model
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
499
B
Parameter List
Содержание P1000
Страница 4: ...This Page Intentionally Blank 4 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 26: ...i 2 General Safety This Page Intentionally Blank 26 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 140: ...4 11 Test Run Checklist This Page Intentionally Blank 140 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 430: ...A 4 Drive Derating Data This Page Intentionally Blank 430 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 504: ...B 16 Defaults by Drive Model This Page Intentionally Blank 504 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 568: ...D 3 UL and CSA Standards This Page Intentionally Blank 568 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 591: ...Index This Page Intentionally Blank YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual 591...
Страница 593: ......