Bias
Output
frequency
Bias value is increased using the
accel/decel times as set in d4-04
Up 2 command
Figure 5.33 Up/Down 2 Bias when d4-03 = 0.00 Hz
Setting d4-03
≠
0.00 Hz
When an Up 2 or Down 2 command is enabled, the bias is increased or decreased in steps for the value set in d4-03. The
frequency reference changes with the accel/decel times determined by parameter d4-04.
Bias
Output
frequency
Up 2 command
Bias value is increased in steps as
defined in d4-03
Drive uses accel/decel times as
set in d4-04
Figure 5.34 Up/Down 2 Bias when d4-03
≠
0.00 Hz
n
d4-04: Frequency Reference Bias Accel/Decel (Up/Down 2)
Determines the accel/decel times used to increase or decrease the frequency reference or bias when using the Up/Down 2
function.
No.
Parameter Name
Setting Range
Default
d4-04
Frequency Reference Bias Accel/Decel (Up/Down 2)
0, 1
0
Setting 0: Current Accel/Decel Time
The drive uses the currently active accel/decel time.
Setting 1: Accel/Decel Time 4
The drive uses accel/decel time 4 set to parameters C1-07 and C1-08.
Note:
The functionality of setting 1 is only accessible via MEMOBUS/Modbus communications.
n
d4-05: Frequency Reference Bias Operation Mode Selection (Up/Down 2)
Determines if the bias value is held when the Up/Down 2 inputs are both released or both enabled. The parameter is effective
only when parameter d4-03 is set to 0.00.
No.
Parameter Name
Setting Range
Default
d4-05
Frequency Reference Bias Operation Mode Selection
(Up/Down 2)
0, 1
0
Setting 0: Hold Bias Value
The bias value will be held if no input Up 2 or Down 2 is active.
Setting 1: Reset Bias Value
The bias is reset to 0% when inputs Up 2 and Down 2 are both on or both off. The drive will use the accel/decel time as selected
in d4-04 to accelerate or decelerate to the frequency reference value.
5.4 d: Reference Settings
188
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Содержание P1000
Страница 4: ...This Page Intentionally Blank 4 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 26: ...i 2 General Safety This Page Intentionally Blank 26 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 140: ...4 11 Test Run Checklist This Page Intentionally Blank 140 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 430: ...A 4 Drive Derating Data This Page Intentionally Blank 430 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 504: ...B 16 Defaults by Drive Model This Page Intentionally Blank 504 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 568: ...D 3 UL and CSA Standards This Page Intentionally Blank 568 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 591: ...Index This Page Intentionally Blank YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual 591...
Страница 593: ......