I/O interface
5
1. I/O interface overview
1.8.4
Stopping due to program interlocks
on
AUTO mode output: DO(10)
off
on
Return-to-origin complete
output: DO(11) off
on
Robot program in-progress
output: DO(13) off
on
Interlock input: DI(11)
off
on
Program start input: DI(12)
off
a ) b ) c ) d ) e ) f ) g ) h ) i )
100ms or more
Program execution
a) Program start input turns on.
b) Robot program in-progress output turns on.
c) Program start input turns off after checking robot program in-progress output is turned
on.
Program stop processing due to interlock
d) Interlock input turns off.
e) Robot program in-progress output turns off.
Program execution after stopping program due to interlock input
f) Interlock input turns on.
g) Program start input turns on.
h) Robot program in-progress output turns on.
i) Program start input turns off after checking robot program in-progress output is turned
on.
* Program will stop if switching to emergency stop. An alarm is output at this time and
the servo-ON output turns off. The servo must be turned on to execute the program
again.
c
CAUTION
• When the program stops during
execution by input of DI11 signal
(Interlock input) or other reason,
the program re-executes the
command that has stopped. Keep
this point in mind when re-
executing the program with DI12
signal (Program start).
Содержание RCX40
Страница 1: ...User s Manual ENGLISH E YAMAHA 4 AXIS ROBOT CONTROLLER E75 Ver 12 00 RCX40 ...
Страница 2: ......
Страница 16: ...viii MEMO ...
Страница 18: ...MEMO ...
Страница 24: ...1 6 MEMO ...
Страница 26: ...MEMO ...
Страница 34: ...MEMO ...
Страница 284: ...MEMO ...
Страница 308: ...5 24 MEMO ...
Страница 310: ...MEMO ...
Страница 318: ...6 8 MEMO ...
Страница 320: ...MEMO ...
Страница 328: ...7 8 MEMO ...
Страница 330: ...MEMO ...
Страница 336: ...MEMO ...