roubleshooting
2. Troubleshooting
2.3
Troubleshooting checkpoints
1. Installation and power supply
1
2
3
Symptom
Controller won't turn on
even with power supplied.
Controller turns on but no
MPB display.
Controller turns on but
“ERR” LED on front panel
lights up.
Possible cause
• Power is not supplied.
• Problem in controller
internal power.
• MPB not connected.
• Wrong MPB connection.
• MPB malfunctioning.
• Problem in controller
internal power supply.
• Now in emergency stop.
• Error of error group No.
17 occurred.
• Error of error group No.
21, 22 occurred.
Corrective action
• Connect power input terminal
correctly.
• Supply rated power supply
voltage.
• Replace the controller.
• Plug in MPB connector
correctly.
• Replace the MPB.
• Replace the controller.
• Release MPB emergency stop
switch.
• Insert MPB connector.
• Connect the emergency stop
terminal of SAFETY
connector.
• Check the axis from the error
information.
• Check the cause from the
error information.
• Eliminate the cause of the
error.
• Check the cause from the
error information.
• Eliminate the cause of the
error.
Check items
• Check power input terminal
connection (L/N/GND).
• Check power input terminal
voltage (L/N/GND).
• Check if “PWR” LED on front
panel is lit.
• Check MPB connector.
• Check how MPB connector is
inserted.
• Replace MPB and check
operation.
• Connect the MPB and check
the error history.
• Check DI00 on MPB screen.
• Connect the MPB and check
the error history.
• Connect the MPB and check
the error history.
Содержание RCX40
Страница 1: ...User s Manual ENGLISH E YAMAHA 4 AXIS ROBOT CONTROLLER E75 Ver 12 00 RCX40 ...
Страница 2: ......
Страница 16: ...viii MEMO ...
Страница 18: ...MEMO ...
Страница 24: ...1 6 MEMO ...
Страница 26: ...MEMO ...
Страница 34: ...MEMO ...
Страница 284: ...MEMO ...
Страница 308: ...5 24 MEMO ...
Страница 310: ...MEMO ...
Страница 318: ...6 8 MEMO ...
Страница 320: ...MEMO ...
Страница 328: ...7 8 MEMO ...
Страница 330: ...MEMO ...
Страница 336: ...MEMO ...