Items
Parameters
Defaults
Description
Warning
Cooling down: The GCB opens and the engine stops after
the configured cooldown time.
Limit
0 to 400 kPa
103 kPa
(14.94 psi,
1.03 bar)
Release the alarm when sensor value is same or lower than
this value and Delay time is over
Items
Parameters
Defaults
Description
Analog input 1 with option "Fuel level"
Input type
Configure dis‐
crete input 4
Fuel level
Configure
discrete
input 4
Type
00 to 07
03 SGD
╚═▷ “4.3.1 Programmable Sensors”
If a type (02 or higher)
with curve is selected:
Curve can be
loaded ...
-/-
Notes
For fuel level curve management and customization.
... and/or edited
(curve)
Low limit warning
0 to 100 %
10 %
Warning alarm will be activated when sensor value is below
the threshold.
Low limit shutdown
0 to 100 %
5 %
Shut down when the sensor value is below the threshold.
Fuel pump control
On
0 to 100 %
25 %
Release the alarm when sensor value is identical to or
below this value and the delay time is over
Off
0 to 100 %
80 %
Cancel the alarm when sensor value is identical to or below
this value and the delay time is over
Fuel tank capacity
enable
Enabled / dis‐
abled
Disabled
Disabled: Fuel tank capacity is displayed in %.
Enable: Additional visualization of fuel tank capacity in
litres (L)
Fuel tank capacity
0 to 10000 L
1000 L
Select the respective fuel tank capacity in litres (L).
Items
Parameters
Defaults
Description
Analog input 2
Input type
Configure dis‐
crete input 5
Temperature
Pressure
Fuel level
Configure
discrete
input 5
Curve type
00 to 07
03 SGD
╚═▷ “4.3.1 Programmable Sensors”
If a type (01 or higher)
with curve is selected:
Curve can be
loaded ...
-/-
Notes
For fuel level curve management and customization.
44
easYgen-400
B37884A
4 Configuration