No.
Items
Description
6
Reserved
7
Open GCB
When close time is set to 0, "open breaker" is disabled
8
Raise speed
Pick-up when enter into warming up time. Disconnect when raise speed
auxiliary input active
9
Lower speed
Pick-up when enter into stop idle or ETS solenoid stop (shutdown alarm).
Disconnect when droop speed auxiliary input active
10
Generator running
Output when genset is running normally, disconnect when rotating speed is
lower than engine speed after fired
11
Fuel Pump Control
Pick-up when the fuel level lower than the open threshold or low fuel level
warning is active; disconnect when the fuel level over the close threshold and
the low fuel level warning input is disabled
12
In operation
Output when it enters into warming up time, and disconnect after cooling
13
Operation mode AUTO
The controller is in Auto Mode
14
Stopping alarm
Output when shutdown alarm occurs and open when alarm is reset.
15
Horn
When shutdown alarm and warn alarm occur, horn output becomes active and
is set for 300 s. During this time, when any panel key or “alarm mute” input
becomes active, the alarm is removed.
16
Heater control
It is controlled by cooler of temperature sensor’s limited threshold
17
Fuel
Action when genset is starting and disconnect when stop is completed
18
Starter
Genset output in start output status and open in other status
19
ECU Stop
Used for ECU engine and control its stop
20
ECU Power Supply
Used for ECU engine and control its power
21
ECU Warning Alarm
Indicate ECU sends a warning signal
22
ECU Shutdown Alarm
Indicate ECU sends a shutdown signal
23
ECU timeout alarm
Indicate controller does not communicate with ECU
24
Speed raise pulse
HIGH for the pre-set »rise speed pulse time« after genset enters into high-
speed warming period and before stop idling
25
Speed lower pulse
HIGH for the pre-set »drop speed pulse time« after entering stop idling
26
Reserved
27
Preheat until safety
FALSE at engine stop. TRUE at engine start. Switch to FALSE when firing speed
has reached (crank disconnected) and additionally Engine monitoring delay
time has expired.
28
Preheat until warming
FALSE at engine stop. TRUE at engine start. Switch to FALSE when firing speed
has reached (crank disconnected) and additionally Engine monitoring delay
time has expired and additionally Warming up time has expired.
29
Preheat until cranking
FALSE at engine stop. TRUE at engine start. Switch to FALSE when firing speed
has reached (crank disconnected).
4.4
Status Menu
General notes
Both HMI and ToolKit-SC offer status information.
61
easYgen-400
B37884A
4 Configuration
4.4 Status Menu