No.
Items
Description
13
Genset Failed
When genset frequency is 0, controller will send a stop alarm signal and it will
be displayed on the LCD.
14
Low Fuel Level
When fuel level low input is active, controller will send a stop alarm signal and
it will be displayed on the LCD.
15
Low Coolant Level
When genset coolant level low input is active, controller will send a stop alarm
signal and it will be displayed on the LCD.
16
Temp. Sensor Open
When sensor hasn’t connected to corresponding port, controller will send
shutdown alarm signal and it will be displayed on the LCD.
17
Oil Sensor Open
When sensor hasn’t connected to corresponding port, controller will send
shutdown alarm signal and it will be displayed on the LCD.
18
Maintenance shutdown
When the genset running time is longer than the maintenance time of the user
setting and maintenance action is set to shutdown, the controller send a
shutdown alarm signal and it will be displayed on the LCD. When the
maintenance action type is set to “Not used”, maintenance alarm resets.
19
Input Shutdown
When the external input is active, the controller will send a shutdown alarm
signal and it will be displayed on the LCD.
20
Over Power
If the over power detection is enabled, the controller will initiate a shutdown
alarm, when it detects that the over power value (power is positive) has
exceeded the pre-set value and the selected action is “Shutdown”.
21
ECU Shutdown
If an error message is received from ECU via J1939, it will initiate a shutdown
alarm.
22
ECU Fail
If the module does not detect the ECU data, it will initiate a shutdown alarm.
9.2
Trouble Shooting
Symptoms
Possible Solutions
Controller has no power.
Check starting batteries; Check controller connection wiring; Check DC
fuse.
Genset shutdown
Check if the water/cylinder temperature exceeds the limits; Check the
genset AC voltage; Check DC fuse.
Controller emergency stop
Check if emergency stop button works properly; Check whether the
starting battery's positive pole is connected to the emergency stop
input; Check whether the circuit is open.
Low oil pressure alarm after crank disconnect
Check the oil pressure sensor and its connections.
High water temp. alarm after crank disconnect
Check the temperature sensor and its connections.
Shutdown Alarm in running
Check the switch and its connections according to the information on
LCD; Check auxiliary input ports.
Fail to start
Check the fuel oil circuit and its connections; Check the starting
batteries; Check the speed sensor and its connections; Refer to the
engine manual.
Starter no response
Check the starter connections; Check the starting batteries.
Genset running while ATS not transfer
Check the ATS; Check the connections between ATS and controllers.
ECU communication failed
Check the CAN connections for high and low polarity; Check if the 120 Ω
resistor is connected properly; Check if the type of engine is correct;
Check if the connections from the controller to the engine and the
output ports settings are correct.
ECU warning or shutdown
Get information from the LCD of the alarm page; If there is a detailed
alarm, check the respective engine. If there is no detailed alarm, please
86
easYgen-400
B37884A
9 Appendix
9.2 Trouble Shooting