Items
Parameters
Defaults Description
Start pause time
3 to 60 s
10 s
The waiting time before second power up when
engine start fails
Engine monitoring
delay time
1 to 600 s
10 s
Alarms for low oil pressure, high temperature,
under speed, under frequency /voltage, charge
fail are inactive.
Start idle time
0 to 3600 s
0 s
Idle running time of genset when starting.
Warm up time
0 to 3600 s
10 s
Warming time between genset switch on and
normal running
Stop timers
Stop delay
0 to 3600 s
1 s
Time from remote start signal is active to start
genset
Cool down time
0 to 3600 s
10 s
Radiating time before genset stop after
unloading
Stop idle time
0 to 3600 s
0 s
Idle running time when genset stops
Stop solenoid hold
0 to 120 s
20 s
The time of powering up the electromagnet
during stop procedure
Stop time of engine
0 to 120 s
0 s
A time accepted for a regular stop to standby.
Activated once the "fail to stop delay" time
(e.g. crank disconnect conditions contain oil
pressure, and oil pressure drops quite slowly if
genset stops) is reached.
Pulse time
Speed raise pulse
0 to 20 s
0.2 s
The "speed raise pulse time" relates to the
output "24 Speed raise pulse" and is active for
the configured time after the starting sequence
"start idle".
Speed drop pulse
0 to 20 s
0.2 s
The speed drop pulse time relates to the output
"25 Speed lower pulse" and is active for the
configured time after the stop sequence "stop
idle".
Crank disconnect
Firing speed RPM
enabled / dis‐
abled
enabled
0 to 3000
r/min
360
r/min
When the generator speed is higher than the
set value, the starter will be disconnected. See
the installation instructions.
Firing speed Hz
enabled / dis‐
abled
enabled
0.0 to 30 Hz
14.0 Hz
When generator frequency higher than the set
value, starter will be disconnected. See the
installation instructions.
Oil Pressure
enabled / dis‐
abled
disabled
49
easYgen-400
B37884A
4 Configuration
4.2.4.2 Configure Engine
Released