No.
Items
Description
5
Shutdown in cooldown
When a high temperature occurs while the engine running and the input is
active, the controller will stop after high speed cooling; When the input is
disabled, the controller will stop immediately.
6
GCB closed
Connect to auxiliary port of gen load breaker.
7
-
-
8
-
Reserved
9
-
Reserved
10
Start request in
In Auto mode, when the input is active, the genset can be started and with
load after genset is OK; when the input is inactive, the genset will stop
automatically.
11
Fuel level warning
Connected to sensor digital input. The controller sends a warning alarm signal
when active.
12
Coolant level warning
13
Fuel level shutdown
Connected to sensor digital input. The controller sends a shutdown alarm
signal when active.
14
Coolant level shutdown
15
-
-
16
Remote control
All buttons on panel are inactive except the four menu buttons to the right of
the display. Additionally, remote mode is displayed on the LCD. Remote mode
can switch module mode and start/stop operation via panel buttons.
17
Charging failure
Connect to failed to charge output.
18
Lock keypad
All buttons in panel are inactive except
19
Alarm Mute
Can deactivate alarm output when input is active.
20
Idle mode
Under voltage/frequency/speed protection is inactive
21
Enable 60Hz
Set »System rated frequency« to default of 60 Hz (e.g. used for CANBUS
engine)
22
Raise speed (ECU)
If ECU type is generic J1939: CAN request increases engine speed in
corresponding speed steps
23
Lower speed (ECU)
If ECU type is generic J1939: CAN request decreases engine speed by
corresponding speed steps
24
Emergency stop
If this signal is active genset will shutdown immediately and Emergency Stop
will be displayed
4.3.3
Programmable Outputs
No.
Items
Description
0
Not Used
Output is disabled when this item is selected.
1
Centralized Alarm
Include all shutdown alarms and warning alarms. When a warning alarm
occurs, the alarm will not self-lock automatically; When a shutdown alarm
occurs, the alarm will self-lock until the alarm is reset.
2
Stop solenoid
Used for the genset with stop solenoid. Pick-up when idle speed is over while
disconnect when ETS delay is over.
3
Idle Control
Used for the genset with idle speed. Pick-up when crank while disconnect
when enter into warming up. Pick-up when stop idle while disconnect when
genset stop completely.
4
Preglow
Close before started and disconnect before powered on
5
Close GCB
When close time is set to 0 s, it is continuous closing
60
easYgen-400
B37884A
4 Configuration
4.3.3 Programmable Outputs