Items
Parameters
Defaults
Description
Open to activate
Open to activate (N.C.): The discrete input is analyzed as
"enabled" by de-energizing the input (normally closed).
Input delay
0.0 to 20.0 s
2.0 s
The input status must be valid for this period of time before
it is released
4.2.4.1.2
Configure Discrete Outputs
Fig. 14:
DC Outputs
[PARAMETER / Configure application / Configure discrete outputs]
Items
Parameters
Defaults
Description
Configure discrete outputs
Notes For discrete outputs 1 to 4:
(Map Programmable
Output)
00 to 26
02 Stop
solenoid
Default of discrete output 1
03 Idle
control
Default of discrete output 2
05 Close
GCB
Default of discrete output 3
06 -
Default of discrete output 4
Notes
╚═▷ “4.3.3 Programmable Outputs”
for details
4.2.4.1.3
Configure Analog Inputs
[PARAMETER / Configure application / Configure inputs/outputs / Configure analog
inputs / ...]
Items
Parameters
Defaults
Description
Temperature
Type
00 to 14
08 SGX
╚═▷ “4.3.1 Programmable Sensors”
42
easYgen-400
B37884A
4 Configuration
4.2.4.1.2 Configure Discrete Outputs
Released