Items
Parameters
Defaults
Description
Action
Not Used/ Warn/
Shutdown
Not Used
Alarm type to be released if limit is same or higher than the
limit value.
4.2.6
Configure Maintenance
[PARAMETER / Configure maintenance]
Items
Parameters
Defaults
Description
Maintenance
Password
0 to 9999
(0-9999)
Notes
Customer-specific password for changing the maintenance
intervall through the HMI.
Select Action
Not used
Warn
Shutdown
Not used
Defines the alarm class if the maintenance is triggered.
[PARAMETER / Configure maintenance interval to change]
Items
Parameters
Defaults
Description
Maintenance interval configured to change
Interval
0 to 5000 h
250 h
Maintenance interval based on operation hours.
Time
Push icon
(current
date)
Maintenance based on internal time.
[PARAMETER / Configure maintenance interval to reset]
Items
Parameters
Defaults
Description
Maintenance interval configured to reset
Interval
0 to 5000 h
250 h
Maintenance interval based on operation hours.
Days
0 to 9999 d
365 d
Maintenance based on days.
Reset maintenance
hours
Enable / Disable
Disable
Reset the maintenance due alarm for hours.
Reset maintenance days
Enable / Disable
Disable
Reset the maintenance due alarm for days.
4.2.7
Configure Counters
[PARAMETER / Configure counters]
Items
Parameters
Defaults
Description
Engine run
Time
0 to 65534 hours
0 hours
Preset value
0 to 59 min
0 min
Preset value
Set (push button)
PUSH: Preset time is written to the connected easYgen
55
easYgen-400
B37884A
4 Configuration
4.2.6 Configure Maintenance
Released