4.2.5.3
Monitoring Engine
Monitoring Speed
[PARAMETER / Configure monitoring / Engine / Speed]
Items
Parameters
Defaults
Description
Overspeed shutdown
Limit
0 to 6000 r/min
1710
r/min
Release the alarm when the MPU speed is same or higher
than this value for 2 seconds.
Action
Not Used/ Warn/
Shutdown
Not Used
Alarm type to be released if limit is same or higher than the
limit value.
Underspeed
shutdown
Limit
0 to 6000 r/min
1200
r/min
Release the alarm when the MPU speed is same or lower
than this value for 10 seconds.
Action
Not Used/ Warn/
Shutdown
Not Used
Alarm type to be released if limit is same or higher than the
limit value.
Loss of speed signal
Delay
0 to 20 s
5 s
Release the alarm when the speed signal (MPU) is not
available for this period of time.
4.2.5.4
Other Monitoring
Monitoring Battery Voltage
[PARAMETER / Configure monitoring / Engine / Other monitoring / Battery voltage]
Items
Parameters
Defaults
Description
Overvoltage
Limit
12.0 to 40.0 V
33.0 V
Release the alarm when sensor value is same or higher
than this value
Action
Not Used/ Warn/
Shutdown
Not Used
Alarm type to be released if limit is same or higher than the
limit value.
Undervoltage
Limit
4.0 to 30.0 V
8.0 V
Release the alarm when sensor value is same or lower than
this value
Action
Not Used/ Warn/
Shutdown
Not Used
Alarm type to be released if limit is same or higher than the
limit value.
Monitoring Charge Alternator (D+)
[PARAMETER / Configure monitoring / Engine / Other monitoring / Charge alternator]
Items
Parameters
Defaults
Description
Charge alternator
(D+)
Charge alternator fail
0.0 to 30.0 V
6.0 V
The allowed maximum difference between the power
supply and D+ voltages.
Release the alarm when the voltage difference exceeds the
set value.
54
easYgen-400
B37884A
4 Configuration
4.2.5.3 Monitoring Engine