No.
Function
Cable
Size
Remarks
7
Aux. Relay
Output 1
1.0 mm²
Rated 1 Adc 24 Vdc, resistive GP
8
Aux. Relay
Output 2
1.0 mm²
Rated 1 Adc 24 Vdc, resistive GP
9
Aux. Relay
Output 3
1.0 mm²
Rated 1 Adc 24 Vdc, resistive GP
10
Aux. Relay
Output 4
1.0 mm²
Rated 1 Adc 24V dc, resistive GP
11
Analog Input 01
1.0 mm²
Connect to fuel level resistance sensor or configure as
discrete input 4 (Ground connected is active)
12
Analog Input 02
1.0 mm²
Connect to temperature, oil pressure, fuel level resistance
sensor or configure as discrete input 5 (Ground connected is
active)
13
Analog Input 03
Engine temp
1.0 mm²
Connect to water / cylinder temp. resistance type sensor
14
Analog Input 04
Oil Pressure
Sensor Input
1.0 mm²
Connect to oil pressure resistance
type sensor
15
MPU+
0.5 mm²
Connected with speed sensor
Note:If no MPU is
installed, parameter
"Firing speed RPM"
([PARAMETER /
Configure
application /
Configure engine /
Configure start/
stop]) must be
disabled.
16
MPU−
0.5 mm²
Connected with speed sensor. A
connection to B- is provided already
internally.
17
NC
Empty terminal
18
NC
Empty terminal
19
CAN H
0.5 mm²
Impedance-120 Ω shielding wire is recommended, its single-
end connect with ground.
20
CAN L
0.5 mm²
Impedance-120 Ω shielding wire is recommended, its single-
end connect with ground.
21
Configurable
Input 1
1.0 mm²
Ground connected is active (B-)
22
Configurable
Input 2
1.0 mm²
Ground connected is active (B-)
23
Configurable
Input 3
1.0 mm²
Ground connected is active (B-)
24
Sensor common
1.0 mm²
Sensor common port
25
easYgen-400
B37884A
3 Installation
3.2 Wiring