• MANUAL (MAN)
•
• STOP
•
• ... and an internal (non) operating phase during the start of the device itself
•
The operation mode can be initiated – provided the current settings allow for this
function:
• directly by pressing the respective button on the front panel
•
• directly by click on the respective button on the ToolKit-SC remote screen
•
• via discrete inputs
•
• via interface
•
5.2.1
Operation Mode AUTO
General notes
In operation mode AUTO, both genset and breaker are under easYgen control. The start
and stopping of the engine is managed automatically, along with opening/closing the
breaker.
• supply load by generator
•
• start the engine
•
• stop the engine
•
5.2.2
Operation Mode MANual
General notes
In operation mode MANual, both genset and breakers are independent of each other
under easYgen control.
The starting and stopping of the engine are managed using the same procedure as in
AUTO mode but without breaker control. Breakers can be opened and closed without
taking care of load or genset state!
CAUTION!
Take care for genset and supply.
5.2.3
Operation Mode STOP
General notes
In operation mode STOP, the breaker is open and the engine is not running.
66
easYgen-400
B37884A
5 Operation
5.2.1 Operation Mode AUTO
Released