No.
Function
Cable
Size
Remarks
25
Generator U
phase Voltage
27 Sensing
Input
1.0 mm²
Connect to U phase output(2 A fuse is recommended)
26
Generator V
phase Voltage
Sensing Input
1.0 mm²
Connect to V phase output(2 A fuse is recommended)
27
Generator W
phase Voltage
Sensing Input
1.0 mm²
Connect to W phase output(2 A fuse is recommended)
28
Generator N2
Input
1.0 mm²
Connect to generator N-wire
29
NC
Empty terminal
30
NC
Empty terminal
31
NC
Empty terminal
32
NC
Empty terminal
33
CT A Phase
Sensing Input
1.5 mm²
Connect secondary coil, rated 5A
34
CT B Phase
Sensing Input
1.5 mm²
35
CT C Phase
Sensing Input
1.5 mm²
36
CT Common
port
1.5 mm²
Refer to Installation description
26
easYgen-400
B37884A
3 Installation
3.2 Wiring
Released