5.3.3
MANual START/STOP
Engine control is separated from breaker management. Breaker(s) must be manually
opened/closed (supply should be in normal range).
⚙
MANual Start
1. ▷
Press the MAN button
▶
The LED next to the button will illuminate to confirm the operation
2. ▷
Press the START button
to start the genset as described above. I case of abnormal
conditions, such as overheating, low oil pressure, over speed and abnormal voltage
during generator running occur, the controller can protect genset by stopping quickly.
⚙
MANual Stop
1. ▷
Pressing
can stop the running generator as described above.
5.4
Transition Procedures
5.4.1
Disconnect during cranking
There are three conditions under control to abort the starting of the engine:
• speed sensor
•
• generator frequency
•
• engine oil pressure
•
They can be used separately or in combinations.
We recommend selecting all three at the same time: engine oil pressure together with
speed sensor, and generator frequency. This allows for an immediate separation of the
starter motor from the engine. Additionally, crank disconnect can be checked exactly.
When set to speed sensor, ensure that the number of flywheel teeth is the same as
setting.
Sensor not used? Make sure not to select a sensor that is not in use. Otherwise, an
error message might occur.
70
easYgen-400
B37884A
5 Operation
5.3.3 MANual START/STOP
Released