Items
Contents
Maximum frequency
Generator: 99.5 Hz
Frequency resolution
0.1 Hz (10 .. 99 Hz)
Frequency accuracy
±0.1 Hz
Nominal CT secondary
rating
5 A
Overload
Measurement
Max.: 10 A
Current Accuracy
1 %
Alternator Frequency
50 Hz/60 Hz
Case Dimension
137 mm × 112 mm × 44 mm
Note: These devices are suitable for flat
surface mounting in a Type 1 enclosure
(UL6200).
Panel Cutout
116.5 mm × 90.5 mm
Working Conditions
Temperature: (−25 to +70) °C;
Humidity: max. 93 %, non-condensing
Storage Condition
Temperature: (−25 to +70) °C
Protection Level against water and dust
Front: IP65 by using mounting material
delivered with device
Back: IP20
Net Weight
0.3 kg
Inputs/Outputs
Items
Contents
Speed Sensor
Voltage
1.0V to 24.0 V (RMS)
Frequency
10,000 Hz (max.)
Start Relay Output
Rated 5 Adc 24 Vdc supply output
Rated 2 Adc 24V dc, inductive (according to
UL 6200)
Fuel Relay Output
Rated 5 Adc 24 Vdc supply output
Rated 2 Adc 24 Vdc, inductive (according to
UL 6200)
Programmable Relay Output 01
1 Adc 24 Vdc, resistive GP (according to
UL 6200)
80
easYgen-400
B37884A
8 Technical Specifications
Released