73
A
B
Boiler water or flow temperature in °C
90
+20
-20
Outside temperature in °C
3.5
1.4
0.2
A
Changing the slope
B
Changing the level (vertical parallel
offset of the heating curve)
Extended menu:
1.
å
2.
"Heating"
3. Select heating circuit.
4.
"Heating curve"
5.
"Slope"
or
"Level"
6. Select heating curve according to the
system requirements.
Connecting the control unit to the LON
The LON communication module
(accessories) must be plugged in.
Installation instructions
LON communication module
Note
The data transfer via LON can take sev-
eral minutes.
Single boiler system with Vitotronic
200-H and Vitocom 200 (example)
Set the LON subscriber numbers and
further functions via code 2 (see the fol-
lowing table).
Note
In the same LON system, the same sub-
scriber number must not be allocated
twice.
Only one Vitotronic may be program-
med as fault manager.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 216 GB
Service
Содержание Vitodens 222-F B2TA series
Страница 12: ...12 2 5 1 4 2x 3 Installing the boiler Removing the front panels 5773 216 GB...
Страница 13: ...13 1 2 SW17 Installing the boiler Siting and levelling the boiler 5773 216 GB Installation...
Страница 19: ...19 2x 4x 4 3 5 2 1 Installing the boiler Opening the control unit casing 5773 216 GB Installation...
Страница 29: ...29 5 4 2 6 2x 3 1 Installing the boiler Closing the control unit casing 5773 216 GB Installation...
Страница 31: ...31 4 1 5 2 2x 3 Installing the boiler Fitting the front panels 5773 216 GB Installation...
Страница 194: ...194 5773 216 GB...
Страница 195: ...195 5773 216 GB...