Coding in the delivered condition
Possible change
A8:1
Heating circuit with mixer
creates a demand for the
internal circulation pump
(only for weather-com-
pensated control units)
A8:0
Heating circuit with mixer
creates no demand for the
internal circulation pump
A9:7
With pump idle time:
Heating circuit pump
"OFF" if the set value is
altered through a change
in operating mode or
through a change in the
set room temperature
(only for weather-com-
pensated control units)
A9:0
Without pump idle time
A9:1
to
A9:15
With pump idle time, ad-
justable from 1 to 15.
1 = short idle period
15 = long idle time
b0:0
Only for heating circuit
with mixer and remote
control:
Heating mode/reduced
mode: Weather-compen-
sated (only for weather-
compensated control
units)
b0:1
Heating mode: weather-
compensated.
Reduced mode: With room
temperature hook-up
b0:2
Heating mode: With room
temperature hook-up
Reduced mode: Weather-
compensated
b0:3
Heating mode/reduced
mode: With room tempera-
ture hook-up
b2:8
Only for heating circuit
with mixer and remote
control, and for the heat-
ing circuit, operation with
room temperature hook-
up must be program-
med:
Room influence factor 8
(only for weather-com-
pensated control units)
b2:0
Without room influence
b2:1
to
b2:64
Room influence factor ad-
justable from 1 to 64. The
higher the value, the great-
er the room influence
b5:0
Only for heating circuit
with mixer and remote
control:
b5:1
to
b5:8
Heating circuit pump logic
function, see the following
table
Code 2
"Heating circuit ..."/group 5
(cont.)
5773 216 GB
Содержание Vitodens 222-F B2TA series
Страница 12: ...12 2 5 1 4 2x 3 Installing the boiler Removing the front panels 5773 216 GB...
Страница 13: ...13 1 2 SW17 Installing the boiler Siting and levelling the boiler 5773 216 GB Installation...
Страница 19: ...19 2x 4x 4 3 5 2 1 Installing the boiler Opening the control unit casing 5773 216 GB Installation...
Страница 29: ...29 5 4 2 6 2x 3 1 Installing the boiler Closing the control unit casing 5773 216 GB Installation...
Страница 31: ...31 4 1 5 2 2x 3 Installing the boiler Fitting the front panels 5773 216 GB Installation...
Страница 194: ...194 5773 216 GB...
Страница 195: ...195 5773 216 GB...