97
Coding in the delivered condition
Possible change
99:0
Do not adjust
9A:0
Do not adjust
9b:70
Set flow temperature for
external demand 70 °C
9b:0
to
9b:127
Set value adjustable from 0
to 127 °C (limited by boiler-
specific parameters)
9C:20
With LON communication
module:
Monitoring LON subscrib-
ers
If there is no response
from a subscriber after
20 min, the values speci-
fied inside the control unit
are used. Only then will a
fault message be issued
(only for weather-com-
pensated control units)
9C:0
No monitoring
9C:5
to
9C:60
Time adjustable from 5 to
60 min
9F:8
Only for heating circuit
with mixer:
Differential temperature
8 K (only for weather-
compensated control
units)
9F:0
to
9F:40
Differential temperature
adjustable from 0 to 40 K
"Boiler"/group 2
Select
"Boiler"
for weather-compensa-
ted control units (see page 89).
Select
"2"
for constant temperature con-
trol units (see page 89).
Coding
Coding in the delivered condition
Possible change
04:1
Minimum burner pause
time subject to the boiler
load (specified by boiler
coding card)
04:0
Systems with low loss
header:
Code 2
"General"/group 1
(cont.)
5773 216 GB
Service
Содержание Vitodens 222-F B2TA series
Страница 12: ...12 2 5 1 4 2x 3 Installing the boiler Removing the front panels 5773 216 GB...
Страница 13: ...13 1 2 SW17 Installing the boiler Siting and levelling the boiler 5773 216 GB Installation...
Страница 19: ...19 2x 4x 4 3 5 2 1 Installing the boiler Opening the control unit casing 5773 216 GB Installation...
Страница 29: ...29 5 4 2 6 2x 3 1 Installing the boiler Closing the control unit casing 5773 216 GB Installation...
Страница 31: ...31 4 1 5 2 2x 3 Installing the boiler Fitting the front panels 5773 216 GB Installation...
Страница 194: ...194 5773 216 GB...
Страница 195: ...195 5773 216 GB...