151
Reheating when DHW is drawn off
When DHW is drawn off, cold water
enters at the bottom of the primary
store.
The heating circuit pump is switched ON
and the 3-way diverter valve is changed
over, if the cylinder temperature sensor
recognises a temperature lower than the
set value.
■ The cylinder primary pump is switched
ON if the boiler water temperature ≥
set DHW temperature.
■ The burner is switched ON if the boiler
water temperature ≤ set DHW temper-
ature, and the cylinder primary pump
is switched ON when the required
boiler water temperature is reached.
DHW is regulated to the set temperature
via the outlet temperature sensor.
The primary store continues to be heated
up after the draw off process has termi-
nated, until the set DHW temperature
has been reached at the cylinder tem-
perature sensor.
The cylinder primary pump and the 3-
way diverter valve remain on for a further
30 s.
Boosting DHW heating
This function is activated by specifying a
second set DHW temperature via coding
address 58 in group
"DHW"
and activat-
ing the fourth DHW phase for DHW heat-
ing.
Heating is boosted during the periods
selected in this time phase.
Function description
Weather-compensated control unit
(cont.)
5773 216 GB
Service
Содержание Vitodens 222-F B2TA series
Страница 12: ...12 2 5 1 4 2x 3 Installing the boiler Removing the front panels 5773 216 GB...
Страница 13: ...13 1 2 SW17 Installing the boiler Siting and levelling the boiler 5773 216 GB Installation...
Страница 19: ...19 2x 4x 4 3 5 2 1 Installing the boiler Opening the control unit casing 5773 216 GB Installation...
Страница 29: ...29 5 4 2 6 2x 3 1 Installing the boiler Closing the control unit casing 5773 216 GB Installation...
Страница 31: ...31 4 1 5 2 2x 3 Installing the boiler Fitting the front panels 5773 216 GB Installation...
Страница 194: ...194 5773 216 GB...
Страница 195: ...195 5773 216 GB...