122
Dis-
played
fault
code
Const.
Weath.-
comp.
System char-
acteristics
Cause
Measures
0F
Control mode
Service
"0F" is only
displayed in
the fault histo-
ry
Service required
Note
After servicing, se-
lect code "24:0".
10
X
X
Controls as if
the outside
temperature
were 0 °C
Short circuit,
outside tem-
perature sen-
sor
Check outside tem-
perature sensor
(see page 139)
18
X
X
Controls as if
the outside
temperature
were 0 °C
Lead break,
outside tem-
perature sen-
sor
Check outside tem-
perature sensor
(see page 139)
19
X
X
Controls as if
the outside
temperature
were 0 °C
Communica-
tion error,
wireless out-
side tempera-
ture sensor
Check wireless
connection (place
wireless outside
temperature sen-
sor close to the
wireless base sta-
tion). Log off out-
side temperature
sensor then log on
again. Replace if
required (see
"Wireless base sta-
tion" installation
and service in-
structions)
20
X
X
Regulates with-
out flow tem-
perature sen-
sor (low loss
header)
Short circuit,
system flow
temperature
sensor
Check low loss
header sensor (see
page 140)
Troubleshooting
Fault codes
5773 216 GB
Содержание Vitodens 222-F B2TA series
Страница 12: ...12 2 5 1 4 2x 3 Installing the boiler Removing the front panels 5773 216 GB...
Страница 13: ...13 1 2 SW17 Installing the boiler Siting and levelling the boiler 5773 216 GB Installation...
Страница 19: ...19 2x 4x 4 3 5 2 1 Installing the boiler Opening the control unit casing 5773 216 GB Installation...
Страница 29: ...29 5 4 2 6 2x 3 1 Installing the boiler Closing the control unit casing 5773 216 GB Installation...
Страница 31: ...31 4 1 5 2 2x 3 Installing the boiler Fitting the front panels 5773 216 GB Installation...
Страница 194: ...194 5773 216 GB...
Страница 195: ...195 5773 216 GB...