102
Parameter
Heating circ pump
Address A3:...
"ON"
"OFF"
–6
–7 °C
–5 °C
–5
–6 °C
–4 °C
–4
–5 °C
–3 °C
–3
–4 °C
–2 °C
–2
–3 °C
–1 °C
–1
–2 °C
0 °C
0
–1 °C
+1 °C
1
0 °C
+2 °C
2
to
+1 °C
to
+3 °C
to
15
+14 °C
+16 °C
Coding in the delivered condition
Possible change
A4:0
With frost protection (only
for weather-compensa-
ted control units)
A4:1
No frost protection; this set-
ting is only possible if code
"A3:–9" has been selec-
ted.
!
Please note
"Important" to ob-
serve for coding ad-
dress "A3".
A5:5
With heating circuit pump
logic function (economy
control): heating circuit
pump "OFF" when the
outside temperature (AT)
is 1 K higher than the set
room temperature (RT
set
)
AT > RT
set
+ 1 K (only for
weather-compensated
control units)
A5:0
Without heating circuit
pump logic function
A5:1
to
A5:15
With heating circuit pump
logic function: Heating cir-
cuit pump "OFF"; see fol-
lowing table
Parameter address
A5:...
With heating circuit pump logic function: Heating cir-
cuit pump "OFF"
1
AT > RT
set
+ 5 K
2
AT > RT
set
+ 4 K
Code 2
"Heating circuit ..."/group 5
(cont.)
5773 216 GB
Содержание Vitodens 222-F B2TA series
Страница 12: ...12 2 5 1 4 2x 3 Installing the boiler Removing the front panels 5773 216 GB...
Страница 13: ...13 1 2 SW17 Installing the boiler Siting and levelling the boiler 5773 216 GB Installation...
Страница 19: ...19 2x 4x 4 3 5 2 1 Installing the boiler Opening the control unit casing 5773 216 GB Installation...
Страница 29: ...29 5 4 2 6 2x 3 1 Installing the boiler Closing the control unit casing 5773 216 GB Installation...
Страница 31: ...31 4 1 5 2 2x 3 Installing the boiler Fitting the front panels 5773 216 GB Installation...
Страница 194: ...194 5773 216 GB...
Страница 195: ...195 5773 216 GB...