Checking flow temperature sensor
Pressure drop curve
10
1
10 30 50 70 90 110
Temperature in °C
0.4
0.6
0.8
2
4
6
8
20
Resistance in k
Ω
Sensor type: NTC 10 kΩ
1.
Remove plug
?
(flow temperature
sensor).
2.
Check the sensor resistance and
compare it with the curve.
Replace the sensor in the case of
severe deviation.
Checking the Vitotronic 200-H (accessory)
The Vitotronic 200-H is connected to the
control unit via the LON cable. To test the
connection, carry out a subscriber check
at the boiler control unit (see page 74).