![Viessmann Vitodens 222-F B2TA series Скачать руководство пользователя страница 79](http://html1.mh-extra.com/html/viessmann/vitodens-222-f-b2ta-series/vitodens-222-f-b2ta-series_installation-and-service-instructions-manual_1017277079.webp)
79
Coding in the delivered condition
Possible change
Internal circulation pump function
51:0
Internal circulation pump
always starts when there
is a heat demand
51:1
System with low loss head-
er:
When there is a heat de-
mand, the internal circula-
tion pump is only started if
the burner is operational.
Circulation pump is switch-
ed off on expiry of run-on
time
51:2
System with heating water
buffer cylinder:
When there is a heat de-
mand, the internal circula-
tion pump is only started if
the burner is operational.
Circulation pump is switch-
ed off on expiry of run-on
time
Subscriber no.
77:1
LON subscriber number
(only for weather-com-
pensated control units)
77:2
to
77:99
LON subscriber number,
adjustable from 1 to 99:
1 - 4 = Boiler
5 = Cascade
10 - 97 = Vitotronic 200-H
98 = Vitogate
99 = Vitocom
Detached house/apartment building
7F:1
Detached house (only for
weather-compensated
control units)
7F:0
Apartment building
Separate adjustment of
holiday program and time
program for DHW heating
possible
Code 1
"General"/group 1
(cont.)
5773 216 GB
Service
Содержание Vitodens 222-F B2TA series
Страница 12: ...12 2 5 1 4 2x 3 Installing the boiler Removing the front panels 5773 216 GB...
Страница 13: ...13 1 2 SW17 Installing the boiler Siting and levelling the boiler 5773 216 GB Installation...
Страница 19: ...19 2x 4x 4 3 5 2 1 Installing the boiler Opening the control unit casing 5773 216 GB Installation...
Страница 29: ...29 5 4 2 6 2x 3 1 Installing the boiler Closing the control unit casing 5773 216 GB Installation...
Страница 31: ...31 4 1 5 2 2x 3 Installing the boiler Fitting the front panels 5773 216 GB Installation...
Страница 194: ...194 5773 216 GB...
Страница 195: ...195 5773 216 GB...