160
External blocking and fault message input
Code
Input DE1
3A:4
Input DE2
3b:4
Input DE3
3C:4
The effect on the internal circulation
pump is selected in coding address
"3E" in group
"General"
.
The effect on the relevant heating circuit
pump is selected in coding address
"d6" in group
"Heating circuit"
.
External demand
The "External demand" function is con-
nected via extension EA1. There are 3
inputs available at extension EA1 (DE1
to DE3).
The function is selected via the following
coding addresses in the
"General"
group:
External demand
Code
Input DE1
3A:2
Input DE2
3b:2
Input DE3
3C:2
The effect on the internal circulation
pump is selected in coding address
"3F" in group
"General"
.
The effect on the relevant heating circuit
pump is selected in coding address
"d7" in group
"Heating circuit"
.
The minimum set boiler water tempera-
ture in case of external demand is selec-
ted in coding address "9b" in group
"General"
.
Venting program
During the venting program, the circula-
tion pump will be alternately switched on
and off for 30 s at a time over a period of
20 min.
For a certain period, the diverter valve is
alternately set towards heating and
DHW heating. The burner is switched off
during the venting program.
Activate venting program: See "Venting
the heating system".
Function description
Control functions
(cont.)
5773 216 GB
Содержание Vitodens 222-F B2TA series
Страница 12: ...12 2 5 1 4 2x 3 Installing the boiler Removing the front panels 5773 216 GB...
Страница 13: ...13 1 2 SW17 Installing the boiler Siting and levelling the boiler 5773 216 GB Installation...
Страница 19: ...19 2x 4x 4 3 5 2 1 Installing the boiler Opening the control unit casing 5773 216 GB Installation...
Страница 29: ...29 5 4 2 6 2x 3 1 Installing the boiler Closing the control unit casing 5773 216 GB Installation...
Страница 31: ...31 4 1 5 2 2x 3 Installing the boiler Fitting the front panels 5773 216 GB Installation...
Страница 194: ...194 5773 216 GB...
Страница 195: ...195 5773 216 GB...