52
5.
Fit thermal insulation ring
D
.
6.
Fit electrodes
B
.
Torque: 4.5 Nm.
Checking and adjusting the ignition and ionisation electrodes
6
+2
0
4
+0.5 0
10
±1
A
A
B
5
+3
0
A
Ignition electrodes
B
Ionisation electrode
1.
Check the electrodes for wear and
contamination.
2.
Clean the electrodes with a small
brush (not with a wire brush) or sand-
paper.
3.
Check the electrode gaps. If the gaps
are not as specified or the electrodes
are damaged, replace the electrodes
together with new gaskets and adjust
them as required. Tighten the elec-
trode fixing screws with 4.5 Nm.
Cleaning the heating surfaces
!
Please note
There should be no scratches or
other damage on the heat
exchanger surface that comes
into contact with hot gases. This
could lead to corrosion damage.
Never use brushes to clean the
heating surfaces.
Brushing can cause existing
deposits to get stuck in the coil
gaps.
Note
Discolouration of the heat exchanger
surface is a normal sign of usage. It has
no impact on the function and service life
of the heat exchanger.
The use of chemical cleaning agents is
not necessary.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 216 GB
Содержание Vitodens 222-F B2TA series
Страница 12: ...12 2 5 1 4 2x 3 Installing the boiler Removing the front panels 5773 216 GB...
Страница 13: ...13 1 2 SW17 Installing the boiler Siting and levelling the boiler 5773 216 GB Installation...
Страница 19: ...19 2x 4x 4 3 5 2 1 Installing the boiler Opening the control unit casing 5773 216 GB Installation...
Страница 29: ...29 5 4 2 6 2x 3 1 Installing the boiler Closing the control unit casing 5773 216 GB Installation...
Страница 31: ...31 4 1 5 2 2x 3 Installing the boiler Fitting the front panels 5773 216 GB Installation...
Страница 194: ...194 5773 216 GB...
Страница 195: ...195 5773 216 GB...