Provisioning and Operating the SSU-2000
Initial Provisioning
96
SSU-2000 User’s Guide
12713020-002-2 Revision D – April 2004
6. Provision the Cyclic Redundancy Check (CRC) for each input port to On or Off.
ICS command:
Type
INPUT xAy CRC
ON|OFF
then press
Enter
, where x is the slot number and y
is the port number.
TL1 command:
See Step 7, below.
7. Provision the Synchronization Status Message (SSM) for each input port to On or
Off. When set to On, the SSU-2000 reads and interprets the SQL on the
reference. If the reference does not include an SSM, the SQL is defined as STU.
ICS command:
Type
INPUT xAy SSM
ON|OFF
then press
Enter
, where x is the slot number and y
is the port number.
For E1 signals, you must define the bit position.
Type
INPUT xAy SSM [4–8]
then press
Enter
.
TL1 commands:
SET-PRMTR-INPUT::S1Ay[-z]:123::,,,ESF|D4|CCS|CAS|1|1.544|2.048|5|
10,ssm,zs,crc,,bit;
where y is the slot number and z is the port number; the numbers indicate the
input frequency in megaHertz; ssm, zs, and crc are ON or OFF, as appropriate.
Bit indicates the position (4–8) of the SSM in E1 signals.
SET-PRMTR-CCINP::S1Ax[-y]:123::,,,zs;
for Composite Clock Input modules, ZS is ON or OFF, as appropriate.
8. Provision the MTIE limits for each input port according to ANSI (PRS or DS1) or
ITU (G.811 or G.823) specifications.
ICS command:
Type
INPUT xAy MTIE
PRS|DS1|G.811|G.823
then press
Enter
where x is the slot number and y is the port number.
TL1 command:
N/A
9. Assign a name, if desired, to each input port. You can assign a name of up to 20
characters.
ICS command:
Type
IONAME xAy [name]
then press
Enter
where x is the slot number and y is the port number.
TL1 command:
N/A
Содержание SDU-2000
Страница 12: ...12 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 18: ...18 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 142: ...Clock Module Reference Data Communications Module 142 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 172: ...Input Module Reference Data Input Adapter Panels 172 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 222: ...Output Module Reference Data Output Adapter Panels 222 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 390: ...SNMP Protocol 390 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 420: ...I O Connector Grounding 420 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 434: ...User Changes to Factory Defaults 434 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...