Installing the SSU-2000
Making Connections
66
SSU-2000 User’s Guide
12713020-002-2 Revision D – April 2004
Power Input
1. Locate the power terminal blocks on the rear panel, as shown in
2. Remove both 5 A fuses. You will replace them at the end of the installation
procedure.
3. Using 16 AWG (minimum) stranded wire, connect primary power to the A-BUS
screws and the secondary power to the B-BUS screws. Symmetricom
recommends that you use a #6 spade lug termination for each power lead.
Figure 2-3.
Power Terminal Blocks
Making Connections
Making I/O Connections
The SSU-2000 shelf has I/O interface connections for connecting the SSU-2000 to
the corresponding I/O adapter panels. Refer to
Chapter 7, Input Module Reference
, and
Chapter 8, Output Module Reference Data,
for information regarding the
different type I/O adapter panels available and the associated cables used to
connect the SSU-2000 to the I/O adapter panels.
shows the rear panel of
the SSU-2000.
Содержание SDU-2000
Страница 12: ...12 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 18: ...18 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 142: ...Clock Module Reference Data Communications Module 142 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 172: ...Input Module Reference Data Input Adapter Panels 172 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 222: ...Output Module Reference Data Output Adapter Panels 222 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 390: ...SNMP Protocol 390 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 420: ...I O Connector Grounding 420 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 434: ...User Changes to Factory Defaults 434 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...