12713020-002-2 Revision D – April 2004
SSU-2000 User’s Guide 273
TL1 Command Interface
The GR-831 format for an autonomous event report is:
<cr lf lf>
^^^sid^date^time <cr lf>
alrmcde^atag^REPT^EVT<cr lf>
^^^”aid:ntfcncde,condtype,srveff,ocrdat,ocrtm:condscr”<cr lf>
where:
sid
is the source ID, and is the assigned name of the unit sending the message
date
is the current date in the format: YY-MM-DD
time
is the current timestamp information in the 24-hour format HH-MM-SS
alrmcde
(Alarm Code) indicates the severity level of the reported alarm or event.
The alarm code is one of these four two-character codes:
*C = critical alarm
** = major alarm
*^ = minor alarm
A^ = non-alarm event
atag
(Alarm Correlation Tag) is a six-digit correlation tag that is incremented each
time a message is sent
REPT
(Report) indicates an autonomous report
AIDTYPE
indicates the cause for the report, such as input signal fault (INP or T1)
or module hardware faults (EQPT)
"response message"
is the response message. The format for the response
message line is:
^^^”[aid]:ntfcncde,condtype,srveff,ocrdat,ocrtm[:condscr]” <cr lf>
where:
–
ntfcncde
(Notification Code) is an optional field that further describes the
alarm or event in an output response or autonomous report, if required.
The notification code is one of these two-character codes:
CR
Critical alarm;
MJ
Major alarm;
MN
Minor alarm:
CL
Cleared alarm;
NA
Event (not an alarm)
–
condtype
(Condition Type) indicates the type of alarm or event that the
message is reporting
–
srveff
(Service Affecting or Not Service Affecting) indicates whether the
response message affects service: SA (Service Affecting response) or
NSA (Not Service Affecting response)
–
ocrdat
(Occurrence Date) indicates the date of occurrence in the format
YY-MM-DD (year, month, day)
Содержание SDU-2000
Страница 12: ...12 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 18: ...18 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 142: ...Clock Module Reference Data Communications Module 142 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 172: ...Input Module Reference Data Input Adapter Panels 172 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 222: ...Output Module Reference Data Output Adapter Panels 222 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 390: ...SNMP Protocol 390 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 420: ...I O Connector Grounding 420 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 434: ...User Changes to Factory Defaults 434 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...