12713020-002-2 Revision D – April 2004
SSU-2000 User’s Guide
69
Installing the SSU-2000
Making Connections
Making Communication Connections
The rear panel of the SSU-2000 shelf has connections for three communications
interfaces, two EIA-232 Serial Port connections, and one Ethernet connection.
These ports allow communication between the SSU-2000 and a terminal or PC.
Each port is configured independently.
for the serial and Ethernet communications port assignments.
EIA232 Serial Port Connections
Both RS-232 serial port connections are made through filtered DE9S female
connectors on the rear panel. These ports allow connection to a terminal or PC for
remote monitoring and control. One is on connector J4 and is labeled Serial Port A,
the other is on connector J5 and is labeled Serial Port B. When connecting to these
ports, use a shielded direct-connect cable with the shield connected to pin 1.
Note: A third EIA-232 serial port may be connected to the
Communications module. Refer to
136, for more information.
Table 2-2. Communications Port Assignments
Port #
Function
Protocol
Serial Ports (EIA-232)
A (J4)
User-selectable as either an ICS or a TL-1 interface. The
port defaults to ICS upon initialization
ICS (Default), TL-1
B (J5)
User-selectable as either an ICS or a TL-1 interface. The
port defaults to ICS upon initialization
ICS (Default), TL-1
Local (Comms
Module)
User-selectable as either an ICS or a TL-1 interface. The
port defaults to ICS upon initialization
ICS (Default), TL-1
Ethernet Ports (Telnet)
23
User-selectable as either an ICS or a TL-1 interface. The
port defaults to ICS upon initialization
ICS (Default), TL-1
123
This port is designated for NTP only
NTP
161
This port is designated for SNMP Interactive
SNMP Interactive
162
This port is designated for SNMP Trap transmission
SNMP Trap
2000
This port is designated for TL-1 only
TL-1
Содержание SDU-2000
Страница 12: ...12 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 18: ...18 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 142: ...Clock Module Reference Data Communications Module 142 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 172: ...Input Module Reference Data Input Adapter Panels 172 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 222: ...Output Module Reference Data Output Adapter Panels 222 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 390: ...SNMP Protocol 390 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 420: ...I O Connector Grounding 420 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 434: ...User Changes to Factory Defaults 434 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...