Technical data
4.5 Unit data
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
73
3-ph. 950 V AC, 2Q and 4Q devices
6RA8096-4MS22-0AA0
6RA8096-4MV62-0AA0
Table 4- 43 Technical data for 3-ph. 950 V AC, 2Q and 4Q devices
Common data
Rated armature supply voltage
1)
V
3-ph. 950 V AC (+15% / -20%)
Rated field supply voltage
1)
V
2-ph. 480 V AC (+10% / -20%)
Electronic power supply,
rated supply voltage
V
2 AC 380 (-25%) to 480 V AC (+10%); In = 1 A or
1 AC 190 (-25%) to 240 V AC (+10%); In = 2 A
(-35% for 1 min.)
With option L05: 18 to 30 DC; In = 5 A
Rated field DC voltage
1)
V
390
Rated frequency
Hz
45 to 65
10)
Overload possibility
6)
Max. 1.8x rated DC current
Closed-loop control constancy
Δ
n = 0.006% of the rated motor speed during operation with
incremental encoder and digital setpoint
Δ
n = 0.1% of the rated motor speed during operation with
analog tachometer or analog setpoint
5)
Degree of protection
IP00 according to EN 60529
Protection class
Class I (with protective conductor system) and class III (PELV)
according to EN 61800-5-1
Table 4- 44 Technical data for 3-ph. 950 V AC, 2200 A, 2Q and 4Q devices
Article number 6RA80 ..
..96-4MS22-...
..96-4MV62-...
Rated DC current
A
2200
2200
Rated DC voltage
1)
V
1140
1000
Rated armature input current
2)
A
1826
1826
Rated power
kW
2508
2200
Power loss at rated DC current (approx.)
W
11340
11340
Rated field DC current
A
40
40
Type of cooling
Forced ventilation
Forced ventilation
Rated fan supply voltage
V
3-ph. 400 V AC (±10%) 50 Hz / clockwise phase sequence
3-ph. 460 V AC (±10%) 60 Hz / clockwise phase sequence
Rated fan current
50 Hz
60 Hz
A
0.95
9)
1.25
0.95
9)
1.25
Fan air flow
m
3
/h
2400
2400
Fan noise level
50 Hz
60 Hz
dB(A)
80.8
83.2
80.8
83.2
Dimensions (WxHxD)
mm
453x883x505
453x883x505
Weight (approx.)
kg
165
185