Descriptions of functions
10.6 Communication via SINAMICS Link
SINAMICS DCM DC Converter
522
Operating Instructions, 12/2018, A5E34763375A
Figure 10-43 SINAMICS Link: Configuration example
10.6.5
Communication failure when booting or in cyclic operation
If at least one sender does not correctly boot after commissioning or fails in cyclic operation,
then alarm A50005 is output to the other nodes: "Sender was not found on SINAMICS Link".
The message contains the number of the faulted node. After you have resolved the fault at
the node involved and the system has identified the node, the system automatically
withdraws the alarm.
If several nodes are involved, the message occurs a multiple number of times consecutively
with different node numbers. After you have resolved all of the faults, the system
automatically withdraws the alarm.
When a node fails in cyclic operation, in addition to alarm A50005, fault F08501 is output:
"COMM BOARD: Monitoring time, process data expired"
At node 1, fault F08501 is not triggered. This node should be used for specifying setpoint
values to other nodes.
Содержание SINAMICS Series
Страница 1: ......
Страница 2: ......
Страница 744: ...Appendix A A 4 Servicing SINAMICS DCM DC Converter 742 Operating Instructions 12 2018 A5E34763375A ...
Страница 758: ......