Type spectrum, ordering information
2.4 Ordering information for options and accessories
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
31
Table 2- 2
Options field
Option
Order codes
2Q field power unit (not possible for 15 A and 30 A devices)
L11
No field power unit (not possible for 15 A and 30 A devices)
L10
Field power unit with 85 A rated current
(possible for devices with rated armature DC current
≥
1500 A, in standard version and with
option L11)
L85
Table 2- 3
Fan options
Option
Order codes
Device without fan
(possible for devices with a rated armature DC current
≥
1500 A)
Note:
The air flow specified in the technical data must be maintained (fan air flow in m
3
/h).
L20
Fan for 1-phase connection
(possible for devices with rated armature DC current 400 A to 1200 A)
L21
Table 2- 4
Additional options
Option
Order codes
Terminal Module Cabinet (TMC)
Can be snapped onto a 35 mm mounting rail.
Enables the simple connection of the CUD standard signals (X177) via spring-loaded
terminals in an easily accessible area of the control cabinet.
The CUD is equipped with an adapter board. Terminal Module Cabinet and connecting cable
(3 m) are supplied separately.
Notes:
•
In the device version with option G63, the X177 terminal connections are no longer
available directly on the CUD.
•
When ordering, please specify which CUD (in the left or right slot) is to be equipped with
the option.
•
If two CUDs are to be equipped with option G63, the option must be ordered for each
CUD.
G63
Armature infeed with extra-low voltage 10 V to 50 V
(possible for devices with rated supply voltage
≤
575 V
L04
Electronic power supply for connection to 24 V DC
L05
Sensor for the air intake temperature
Possible as of firmware version 1.3 HF1
L15
Coated modules
Coated modules increase the degree of ruggedness with respect to climatic effects:
Relative / absolute humidity 5% to 95% / 1 to 29 g/m
3
for ambient temperature or cooling
medium temperature ≤
30 °C
≤
60% with the occurrence of SO
2
and H
2
S and/or for ambient temperature or cooling
medium temperature 30 °C to 40 °C
Oil mist, salt mist, formation of ice, condensation, dropping, spray, splashing and jet-water not
permissible.